4.6

Map Descriptor Examples

This example shows the transfer of I/O data with Remote PROFIBUS DP Slaves using Station Addresses
of 1 and 125.
Map Descriptor
Map_Descriptor_Name
, Data_Array_Name
Word_In_003
, Word_Input
Word_Out_003
, Word_Output
Byte_In_125
, Byte_Input
Byte_Out_125
, Byte_Output
, PROFIBUS_Data_Type
, Address
, Word
, 0
, Word
, 0
, Byte
, 0
, Byte
, 0
If the device only has an input buffer:
Map
Descriptor
Map_Descriptor_Name
, Data_Array_Name
Word_In
, Word_Input
Byte_In
, Byte_Input
, PROFIBUS_Data_Type
, Address
, Word
, 0
, Byte
, 0
If the device only has an output buffer:
Map Descriptor
Map_Descriptor_Name
, Data_Array_Name
Word_Out
, Word_Out
Byte_Out
, Byte_Out
, PROFIBUS_Data_Type
, Address
, Word
, 0
, Byte
, 0
If the device has both an input and an output buffer:
Map Descriptor
Map_Descriptor_Name
, Data_Array_Name
Word_In
, Word_Input
Word_Out
, Word_Output
Byte_In
, Byte_Input
Byte_Out
, Byte_Output
, PROFIBUS_Data_Type
, Address
, Word
, 0
, Word
, 0
, Byte
, 0
, Byte
, 0
The table below shows the map descriptor function that to use in the config.csv with a specific module.
A PROFIBUS Slave device will have one of three types of I/O Modules, Input, Output or Input/Output. The
I/O Module type can only be found by analyzing the GDS file of the device in a PROFIBUS Software
system.
4
Two Map Descriptors need to be configured, one for the input module and one for the output.
, Data_Array_Offset
, Function
, 0
, Rdbc
, 0
, Wrbc
, 0
, Rdbc
, 0.
, Wrbc
, Length
, Scan_Interval
, 50
, 1s
, 50
, 1s
, 120
, 1s
, 120
, 1s
, Data_Array_Offset
, Function
, 0
, Rdbc
, 0
, Rdbc
, Length
, Scan_Interval
, 50
, 1s
, 120
, 1s
, Data_Array_Offset
, Function
, 0
, Wrbc
, 0
, Wrbc
, Length
, Scan_Interval
, 50
, 1s
, 120
, 1s
, Data_Array_Offset
, Function
, 0
, Rdbc
, 0
, Wrbc
, 0
, Rdbc
, 0
, Wrbc
, Length
, Scan_Interval
, 50
, 1s
, 50
, 1s
, 120
, 1s
, 120
, 1s
Module
Map Descriptor Function
In
Rdbc
Out
Wrbc
In/Out
Wrbc/Rdbc
4
Page 9 of 14
PROFIBUS DP Master Driver Manual
, Node_Name
, PDP_SLV003
, PDP_SLV003
, PDP_SLV125
, PDP_SLV125
, Node_Name
, PDP_SLV003
, PDP_SLV003
, Node_Name
, PDP_SLV003
, PDP_SLV003
, Node_Name
, PDP_SLV003
, PDP_SLV003
, PDP_SLV003
, PDP_SLV003