PEAK® IOM57 Input/Output Modules
Installation Instructions
PK-IOM5711, PK-IOM5731
Application
The PEAK IOM57 field controllers belong to the PEAK Controller family. Input/Output Module (IOM) controllers
expand the number of points that are connected to an OEM SMART Equipment controller (PEAK) to monitor and
control a wide variety of HVAC/R equipment.
PEAK IOM57 field controllers operate on an RS-485 BACnet® MS/TP bus as BACnet Application Specific
Controllers (B-ASCs) and integrate into Johnson Controls® and third-party BACnet systems.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when this equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual,
may cause harmful interference to radio communications. Operation of this equipment in a residential area may
cause harmful interference, in which case users will be required to correct the interference at their own expense.
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur
du Canada.
Installation
Observe the following guidelines when you install a field controller:
Transport the controller in the original container to minimize vibration and shock damage.
Verify that all parts shipped with the controller.
Do not drop the controller or subject it to physical shock.
Parts included
One controller with removable terminal blocks. Power, sensor actuator (SA), and field controller (FC) bus are
removable.
One installation instructions sheet.
Materials and special tools needed
Three fasteners appropriate for the mounting surface (M4 screws or #8 screws).
One 20 cm (8 in.) or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount (only).
Small straight-blade screwdriver to secure wires in the terminal blocks.
PEAK® IOM57 Input/Output Modules Installation Instructions
*2410143985C*
Part No. 24-10143-985, Rev. C
1
24-10143-985, Rev. C
(barcode for factory use only)
Issued June 2018

Advertisement

Table of Contents
loading

Summary of Contents for Peak PEAK IOM57

  • Page 1 The PEAK IOM57 field controllers belong to the PEAK Controller family. Input/Output Module (IOM) controllers expand the number of points that are connected to an OEM SMART Equipment controller (PEAK) to monitor and control a wide variety of HVAC/R equipment.
  • Page 2: Din Rail Mount Applications

    • Mount the controller in an area that is free of corrosive vapors, and observe the ambient conditions requirements in PEAK IOM57 Series technical specifications. • Provide for sufficient space around the controller for cable and wire connections to ensure easy cover removal and good ventilation through the controller (50 mm [2 in.] minimum on the top, bottom, and front of the...
  • Page 3: Wall Mount Applications

    IMPORTANT: Do not overtighten the mounting screws. Overtightening the screws may damage the mounting clips. Figure 2: PEAK IOM5711 physical features Table 1: PEAK IOM5731 physical features (Part 1 of 2) Callout Physical feature: description and references Device address DIP switch block...
  • Page 4 Table 1: PEAK IOM5731 physical features (Part 2 of 2) Callout Physical feature: description and references SA bus or FC bus Universal inputs (UI) (not available on IOM5731) End-of-Line (EOL) switch (located under the cover) SA bus or FC bus port (RJ-12 6-pin modular jack)
  • Page 5: Terminal Blocks And Bus Ports

    Most of the input terminal blocks are mounted on the bottom of the controller and the output terminal blocks are mounted on the top of the controller. See Table 4 for more information about I/O terminal functions, requirements, and ratings. PEAK® IOM57 Input/Output Modules Installation Instructions...
  • Page 6 The SA/FC bus port on the front of the controller is an RJ-12, 6-position modular jack that provides a connection for devices on the SA bus, a Wireless Commissioning Converter, ZigBee® wireless dongle, or a ZFR1811 Wireless Router, depending on which bus the IOM is operating on. PEAK® IOM57 Input/Output Modules Installation Instructions...
  • Page 7 IMPORTANT: Connect 24 VAC supply power to the controller and all other network devices so that transformer phasing is uniform across the network devices. Powering network devices with uniform 24 VAC supply power phasing reduces noise, interference, and ground loop problems. The controller does not require an earth ground connection. PEAK® IOM57 Input/Output Modules Installation Instructions...
  • Page 8: Wireless Network Applications

    See the figures in this section for the applicable termination diagrams. Table 3: Termination details (Part 1 of 3) Type of field device Type of Input/ Termination diagrams Output Temperature sensor Voltage input - external source Voltage input - internal source PEAK® IOM57 Input/Output Modules Installation Instructions...
  • Page 9 Type of Input/ Termination diagrams Output Voltage input (self-powered) Current input - external source (isolated) Current input - internal source (2 wire) Current input- internal source (3 wire) Current input - external source (in loop) PEAK® IOM57 Input/Output Modules Installation Instructions...
  • Page 10 Table 3: Termination details (Part 3 of 3) Type of field device Type of Input/ Termination diagrams Output Feedback from EPP-1000 Dry contact Dry contact Voltage (analog output) 0-10 VDC output to actuator (internal source) PEAK® IOM57 Input/Output Modules Installation Instructions...
  • Page 11: Terminal Wiring Guidelines, Functions, Ratings, And Requirements

    Internal 11 V, 15k ohm pull up ICOMn Universal input common for all universal input terminals Same as (universal) INn Note: All universal ICOMn terminals share a common, which is not isolated from all other commons. PEAK® IOM57 Input/Output Modules Installation Instructions...
  • Page 12 Isolation insulation exists within the two groups. For example, 24 V I/O can connect to OUT1 through OUT4, and high voltage I/O can connect to OUT5 through OUT8. Note: You cannot mix voltage levels within the groups. PEAK® IOM57 Input/Output Modules Installation Instructions...
  • Page 13: Cable And Wire Length Guidelines

    0.8 mm (20 AWG) 61 m (200 ft) 45.7 m (150 ft) 0.6 mm (22 AWG) 30.5 m (100 ft) N/A (24 AWG ) 15.2 m (50 ft) 0 m (0 ft) Load Current (mA) PEAK® IOM57 Input/Output Modules Installation Instructions...
  • Page 14: Sa/Fc Bus And Supply Power Wiring Guidelines

    Setting the device addresses PEAK field controllers are master devices on MS/TP (SA or FC) buses. Before operating controllers on a bus, you must set a valid and unique device address for each controller on the bus. You set a controller's device address by setting the positions of the switches on the DIP switch block at the top of the controller (Figure 9).
  • Page 15 Note: PEAK field controllers ship with switch 128 ON and the remaining address switches off; this renders the controllers wired subordinate devices, which do not operate on MS/TP buses, but will not interfere with bus operation.
  • Page 16: Removing The Controller Cover

    Reserved addresses for wired subordinate devices (not for use on controllers) (Switch 128 ON) Note: PEAK controllers ship with switch 128 ON and the remaining address switches off rendering the controllers wired subordinate devices, which do not operate on MS/TP buses.
  • Page 17: Setting The End-Of-Line (Eol) Switch

    EOL switch to Off. When a controller is connected to power with its EOL switch set to ON, the amber EOL LED on the controller cover lights up. PEAK® IOM57 Input/Output Modules Installation Instructions...
  • Page 18: Commissioning The Controllers

    Table 10: Accessories ordering information (Part 1 of 2) Product code number Description MS-BTCVT-1 Bluetooth® Wireless Commissioning Converter MS-ZFR1811-0 Wireless Field Bus Router TP-2420 Transformer, 120 VAC Primary to 24 VAC secondary, 20 VA, Wall Plug PEAK® IOM57 Input/Output Modules Installation Instructions...
  • Page 19: Technical Specifications

    Replacement FC bus terminal blocks, 4-Position, blue, bulk pack AP-TBK3PW-0 Replacement power terminal blocks, 3-Position, gray, bulk pack Technical specifications PEAK IOM57 Series technical specifications (Part 1 of 2 ) Product code numbers PK-IOM5711 Series Input/Output Module PK-IOM5731 Series Input/Output Module...
  • Page 20 PEAK IOM57 Series technical specifications (Part 2 of 2 ) Mounting Screw mount on flat surface with three integral mounting clips on controller or horizontally mounted on single 35 mm DIN rail mount (preferred) inside a supplementary enclosure minimum IP20 rating that only qualified personnel can access.
  • Page 21 Building Technologies & Solutions 507 E. Michigan Street, Milwaukee, WI 53202 PEAK® and Johnson Controls® are registered trademarks of Johnson Controls All other marks herein are the marks of their respective owners. © 2018 Johnson Controls PEAK® IOM57 Input/Output Modules Installation Instructions Published in U.S.A.