Overview

The DIN InFusion™ Controller is part of the family of the most
powerful automation controllers on the market, featuring an
extremely fast processor, fast Bus communication, large
memory capacity, a built-in Ethernet jack and a USB port. Just
one DIN Infusion Controller supports up to 120 WireLink™
stations and up to 120 RadioLink™ stations. The DIN InFusion
Controller is the main "CPU" of Vantage's most advanced
lighting System. It mounts to standard 35mm DIN rail. An LCD
interface provides immediate status and diagnostics. A Lithium
battery retains time and system status in a power outage. The
processor has real time and astronomical time clocks. Design
Center software is used to program the Controller. The
Controller runs independent of a PC after initial setup and
programming. Application code is upgradeable through Design
Center Software. InFusion Controllers operate as stand-alone
or networked. *The Vantage InFusion Controller Network can
consist of up to thirty-one Controllers in a single Network.
*15 Controllers maximum on each Controller to Controller Bus
run. Up to 31 Controllers are allowed when connected via
Ethernet.
Ethernet Port ● Standard USB Port ● Five Embedded RS-232
Ports ● Two RS-485 Ports ● Manual Override (front panel
buttons) ● Addressable (front panel buttons) ● Network
Termination Switch ● Reset Switch ● Built-in Protection ●
electrically isolated between controllers
DIN InFusion Controller Specifications
Dimensions HWD
Weight
Mounting
Power Requirement
Lightning / Surge Protection
Max. Length of Each Controller
to Controller Bus Network
Wiring config. C2C, IC Network
Station Bus Specification
Station Bus Power Supply with
200W/36VDC/5.5A source
Station Bus Power Supply with
60W/24VDC 2.5A source
Max. # WireLink Stations 36V
Max. # WireLink Stations 24V
Max. Wire Length Station Bus
Wire Configuration of Station
Bus
Ambient Operating
Temperature
Ambient Operating Humidity
Cooling
Lithium Battery Backup
*CAUTION: 36V stations have a
Number sticker. Any station, not displaying this symbol, should
not be connected to a 36Volt Station Bus.
86 x 157 x 58mm
417 g
35 mm DIN Rail (EN 50 022: 1977)
36VDC/5.5A or 24VDC/2.5A
Static Shock IO. All ports and case,
IEC 61000-4-2
Low Voltage, ITU-T K.20
2000 feet / 609 meters- using
16-18AWG 2-conductor, twisted pair,
non-shielded wire
Daisy Chain
2C 16AWG, non-shield, <30pF per foot
Station Bus should be separated a
minimum of 18" from other parallel
communication and/or high voltage
runs.
One 60W independent power supply to
each station bus.
One 35W shared power supply to both
station buses.
Up to 60 Stations each bus or until the
independent 60W supply is used on
each bus
Up to 50 Stations each bus or until the
shared 35W supply is used
2,000 feet of cabling max. on each
station bus. No station more than 1,000
feet from Controller.
Daisy Chain, Branch, Star
0-40°C / 32-104°F
5-95% non-condensing
Convection
Disk battery CR2032, 3Volt
2.5 yrs. un-powered or 30 yrs. powered
(field replaceable – See Caution at end)
symbol on the Serial
I N S T A L L A T I O N
DIN InFusion Controller — MODEL: IC-DIN

Software/Firmware

Design Center Software must be used to program the
controller.
Design Center Software requires Windows XP.

Installation

Installation of Vantage products should be performed or
supervised by a Certified Vantage Installer. It is mounted on a
standard 35 mm DIN Rail in any standard DIN Enclosure. All
connections to the Controller are wired to removable screw
terminal connectors.

Powering The DIN Controller

The DIN Controller must be wired to a 200W, 36VDC or
24VDC power supply. Vantage can supply a DIN power
transformer part number #ACPDXXSM2. This power supply is
rated: Input, 120/230Vac, Output, DC 24V/2.5A and is DIN rail
mountable. Before using pull out the lithium battery tab
insulator on the DIN Controller. Connect the plus side of the
DC transformer to the 24V/36V screw terminal and the
negative side to one of the ground terminals. Connect another
wire from the second ground terminal to the enclosure ground,
earth ground.
NOTE: This earth grounding on the DIN Controller and power
supply should be the ONLY earth ground connection in this
DIN Controllers immediate system. Controller Bus (connections
between controllers) connections are isolated so a new earth
ground reference for each Controller is normal.

Controller Address

The DIN Controller's address is no longer selected by adjusting
the turn dials for the correct address. The address is now
assigned through the front panel buttons on the DIN
Controller.
Follow these steps to set the Controller Address:
With the Controller on screen 1 (HOME), press any
button on the front of the Controller
th
Press the 4
button under "C2C"
Press the second button under "Next" until the cursor is
at the Controller number, "C#" for 10s place and again
for 1s place.
Press the button under "Adj" until the address is correct.
Valid addresses are from 01 to 31.
Press the button under "Set" to save the setting
The DIN Controller will reboot with the new address on
screen 1 (HOME) as shown below

InFusion DIN Controller Setup in Design Center

Every new project in Design Center automatically includes an
InFusion Controller. Change the Controller to IC-DIN at the
beginning of the project, and select if it will have a 36VDC or
24VDC power supply. Design Center 2.3 and higher allows a
DIN controller to be setup as default under Settings | System
Preferences | Default Controller Type. Additional controllers
are added automatically as the project grows, however it is
possible to add additional Controllers at any time. Remember
to select the proper Controller, i.e., IC-DIN, IC-36V or IC-
24V.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DIN InFusion IC-DIN and is the answer not in the manual?

Questions and answers

Summary of Contents for Vantage Hearth DIN InFusion IC-DIN

  • Page 1 I N S T A L L A T I O N V A N T A G E C O N T R O L S . C O M DIN InFusion Controller — MODEL: IC-DIN 1061 South 800 East • Orem, Utah 84097 • Telephone 801 229 2800 • Fax 801 224 0355 Overview Software/Firmware The DIN InFusion™...
  • Page 2 Programming the InFusion Controller two would have the Controller Network Termination switch All programming is created in InFusion Design Center ON, the other three must be OFF. software. Projects should be saved regularly when being Example 2: In a ten Controller system, let’s say enclosures 1 created.
  • Page 3 • SCREEN 9 (cont.) – Flash – Free Memory / Total Memory Channels: Flash memory is like the Hard-Drive on a computer. This is the main memory storage area for all programming. Data is compressed when downloaded. • Refresh – updates (live) this screen, buttons 1 or 2. •...
  • Page 4 Remote Access Port Settings Make sure that you are allowing the Ping operation as this is In order to access the InFusion Controller outside the home used by InFusion to verify its connection. network (for remote programming), you will need to forward internet ports 2001 and 3001 from the router or modem, that is At your remote location, enter in the IP Address, assigned from connected to the internet, to the IP address of the InFusion...

Table of Contents