Magic-Pak MGE4 Series Installation And Maintenance Instructions Manual page 3

Gas heating with electric cooling unit

Advertisement

Clearance to combustible materials is 0" at the side,
top, and front of plenum. If accessibility clearances
are greater than clearances to combustibles,
accessibility clearances take precedence.
The front of the unit must be accessible for service.
If the unit is enclosed, providing a door or access
panel opposite the front of the unit is the preferred
method of providing access. The door or access
panel must be at least 30" wide (centered on the
unit) and as tall as the unit.
Minimum Unit Clearance
Front*
1"
* Added clearance must be provided for the
gas supply line and drain trap installation.
IMPORTANT
The unit must be installed with approved wall sleeve
and grille accessories for safe operation. Improper
installations could result in property damage, personal
injury, or death.
Platform (field supplied) must be level with sill plate of hole in exterior wall. Unit must be
507858-01
Sides
1"
Exterior Wall
Wall Sleeve
(one each side)
Sill Plate
supported by platform.
Figure 1. Minimum Clearances
Issue 1922
Top View
Return Duct
Opening
1"
Min.
Front of Unit
Side View
4" Min.
Supply Duct
Opening
1"
Min.
Clearance to
Front of Unit*
Interior Wall
Front of Unit
Clearances*
Mounting Strap
(one each side)
3/4" Plywood Riser
Floor
Page 3 of 21