Start-Up; Operation - Magic-Pak MGE4 Series Installation And Maintenance Instructions Manual

Gas heating with electric cooling unit

Advertisement

Thermostat
The room thermostat should be located on an inside
wall where it will not be subject to drafts, sun exposure,
or heat from electrical fixtures or appliances. Follow
manufacturer's instructions enclosed with the thermostat
for general installation procedures. Color-coded insulated
wires (#18 AWG) should be used to connect the thermostat
to the unit.

Start-Up

For Your Safety, Read Before Lighting
If you do not follow these instructions exactly, a fire
or explosion may result causing property damage,
personal injury, or loss of life.
This furnace is equipped with a direct ignition control.
Do not attempt to manually light the burners.
To Light Burners
1.
Turn off electrical power to unit.
2.
Turn the thermostat to lowest setting.
3.
Move the gas valve switch to the "ON" position (see
Figure 8).
4.
Turn on electrical power to the unit.
5.
Set the room thermostat to the desired temperature.
If the thermostat "set" temperature is above room
temperature after the pre-purge time expires, burners
will light.
Regulator
Adjustment
Screw
(Under Cap)
Figure 8. Gas Valve
507858-01
WARNING
CAUTION
Gas Manifold
Pressure
Test Tap
ON / OFF
Switch
Gas Inlet
Pressure
Test Tap
Gas Inlet
To Shut Down Unit
1.
Turn off electrical power to unit.
2.
Move the gas valve switch to the "OFF" position (see
Figure 8).

Operation

Operation of the unit is automatic and will provide heating
and cooling depending on the setting of the thermostat.
Heating
1.
Turn on main power supply.
2.
Open manual gas shutoff valve.
3.
Set thermostat system to "HEAT".
4.
Set thermostat to temperature desired.
Sequence of Operation
1.
Thermostat calls for heat.
2.
Combustion blower starts and proper air flow is proven
by the pressure switch closing.
3.
Blower continues to operate for 30 seconds prior to
the burners lighting.
4.
Ignition control begins spark and opens gas valve. The
burners are lit. Ignition is proved through flame sensor.
5.
Circulating air blower starts 30 seconds after the
burners light.
6.
When the thermostat is satisfied, the burners and
combustion blower shut off.
7.
Circulating air blower will shut off 120 seconds later.
If the burners should fail to ignite, the ignition control will
try to ignite the burners a total of three times. Should the
burners fail to ignite within the three trials for ignition, the
ignition control will lock out for 1 hour before beginning
another ignition cycle. To reset the control, turn the
thermostat down or off for 10 seconds and then set to
desired setting. At this time, the ignition sequence will try
again.
Cooling
1.
Set thermostat system switch to "COOL."
2.
Set thermostat to temperature desired.
NOTE: When Y is energized, the combustion blower will
operate for 10 seconds. The purpose of this action is to
deter insect nesting in the flue pipe.
To Shut Down Unit
For temporary or short periods of shutdown, set the
thermostat system switch to "OFF". For a prolonged period
of shutdown, set the thermostat system switch to "OFF"
and turn off the electrical power supply and the gas supply
to the unit.