Operating and mounting manual (translation) Operating and mounting manual Safety shut off valve gas – solenoid valve Contents General Remarks Valve data Application Danger Notices Safety terms Safety notice Qualified staff Unauthorized modification and spare part production Unauthorized operation Safety information for the use in explosion-prone areas guideline 94/9/EC Handling Transport Storage...
Operating and mounting manual (translation) 1.0 General Remarks This operating manual includes instructions to assemble and operate the valve in the prescribed and safe way. Additionally, the adeqaute operating instructions (BTA) of each special solenoid drive must be considered. Series MG... 220.100.038 Series MG...X 220.000.040...
Operating and mounting manual (translation) Threaded connection dimension at DIN ISO 228-1 Connection G 1 1/4 1 1/2 120-EVS 135-EVS O Acceptance test certificate 3.2 possible, - not available, Voltage: 24V– 420V (–15% to +10%) Protection type: IP54 or IP65 Frequency 40 –...
Operating and mounting manual (translation) These are persons who are familiar with erection, assembly, starting, operation and maintenance of the product and who have special qualifications acc. to their activities and functions, e.g.: Instruction and obligation to carry out and meet all regional and in-house orders and requirements.
Operating and mounting manual (translation) The goods must be checked on completeness and transport damage. See also section 9.0 Storage If the valve is not installed immediately after delivery, it must be stored properly. Storage temperature -20°C up to + 60°C, dry and clean. ...
Operating and mounting manual (translation) Starting torque, product screws and nuts greased Screw Torque Marking The type sign on the solenoid drive has the following information: Fabricator Valve type, nominal width, pressure and temperature indication, fitting position Year of construction/ production no.
Operating and mounting manual (translation) NOTICE! Please observe the solenoid drive operating instructions (BTA). 6.0 Operation DANGER! Before commissioning a new installation or before starting up an installation again after repairs or modifications, ensure: The proper completion of all installation and assembly work! ...
Operating and mounting manual (translation) Check the data on material, pressure, temperature, voltage and flow direction with the layout plan of the pipework system. In addition, check whether the operating conditions correspond to the technical data in the data sheet or on the rating plate. Troubleshooting plan Malfunction Possible causes...
Operating and mounting manual (translation) If the sealing element becomes damaged (only applies to flange version Fig.1), the spare parts kit should be used. Flanged version Fig.1 16/25-EVS Loosen set screw (941) and unscrew upper part (106). Remove stud (902) together with safety ring (944) and place solenoid core (207) together with spring pin (210), valve pin (214), pressure spring (503), hex.
Operating and mounting manual (translation) company, the railway company or the shipping agent as otherwise all claims for damages against these companies will be voided. 10.0 Explanations on Codes and Directives The Council of the European Community has passed common guidelines for the free exchange of goods within the Community;...