IBM DS8900F Introduction And Planning Manual page 111

Table of Contents

Advertisement

Table 47. DS8900F power cords (continued)
Power cord feature
code
1042
1043
1044
Notes:
1. The customer connector must be IEC 60309-compliant. Power cords that are used with DS8100, DS8300,
DS8700, DS8800, DS8870, and DS8880 cannot be used again with the DS8900F.
2. Power cords without inline connectors are rated at 600 V AC. Other power cords are rated as described in
the table. Single-phase power cord has 2W+G configuration.
3. The conductor size for single-phase power cords is 10 AWG.
4. Power cords that exit the bottom are 4.2 m (14 ft) from the lowest point where they exit the frame to the
mating face of the plug or bare leads. Power cords that exit the top are 1.8 m (6 ft) from the highest point
from the frame to the mating face of the plug or bare leads.
5. The IEC60309 receptacle must be installed in a metal-backed box with the green wire ground-connected to
the grounding lug within the box. Ensure continuity between the box and the metallic shielding of the liquid-
tight conduit.
6. The descriptions indicate the line cord rating and are not an indication of system power rating. The cord
rating defines the maximum breaker rating for the line cord (60A with connector, 63A without connector).
Downstream components are designed for fault currents consistent with facility circuit breaker ratings up to
63A.
Power consumption and environmental information
When you are planning to meet the power requirements for the DS8000 series, consider the power
consumption and other environmental points of the storage system.
Note: The power consumption for the operating disk enclosure is typically 275 watts - 300 watts. The
power consumption for the operating High Performance Flash Enclosure Gen2 is 500 watts.
The power consumption and environmental information for the IBM DS8000 is provided in Table 48 on
page 97.
Table 48. Power consumption and environmental information for models 993, 994, 996, and E96
Measurement
1, 2
Peak electric power
Thermal load
Capacity of exhaust
Ground leakage current
Startup current
Power cord description
6
Single-phase power cord, 250 V, 32
A, for use in Australia and New
Zealand
Single-phase power cord, 250 V, 30
A, for use in Korea
Single-phase power cord, 250 V, 32
A, IEC-309 (halogen free)
Unit of measure
Kilowatt (kW)
British thermal units
(BTU) per hour
cubic meters per minute
(cubic feet per minute or
CFM)
milliamperes (mA)
amperes (A or amp)
Inline connector/
Receptacle
56P332/56CV332
KP 32A/KP
332P6W/332R6W
Base frame
Model 993: 2.2; Model
994: 4.6; Model 996: 5.9
Model 993: 7464; Model
994: 15682; Model 996:
20199
44.2
(1500)
< 21
≤ 100
Chapter 6. Delivery and installation requirements 97
Wire gauge
10 AWG
10 AWG
10 AWG
Expansion frame
Model E96: 3.9
Model E96: 13320
51.8
(1800)
< 21
≤ 100

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents