Beko DRYPOINT RA 3 Installation And Operation Instructions Manual page 33

Compressed-air refrigeration dryer
Table of Contents

Advertisement

 If installed:
the P
low-pressure
B
switch has triggered.
 If installed:
the T
safety tempera-
S
ture switch is trig-
gered.
 DMC14 The
LED
of the device is on or
flashes to indicate
alarm situations.
DRYPOINT® RA 3-160
2. The condenser is dirty – please clean it (air-cooled).
3. The condenser fan does not work – see the corresponding point (air-cooled).
4. The cooling water is too hot – re-establish the nominal conditions (water-cooled).
5. The cooling-water flow is insufficient – re-establish the nominal conditions (water-cooled).
Reset the pressure switch by pressing the button on the controller itself – check the
perfect functioning of the dryer.
The PA pressure switch is defective – contact a BEKO service technician regarding
the replacement.
There is a leak in the refrigeration cycle – please contact a BEKO service technician.
The pressure switched is automatically reset when the normal conditions have been
re-established – check the proper operation of the dryer.
Check which of the following reasons is responsible for the triggering:
6. Excessive thermal load – re-establish the standard operating conditions
7. The inlet air is too hot – re-establish the nominal conditions.
8. The ambient temperature is too high or the room ventilation insufficient – ensure sufficient
ventilation.
9. The condenser unit is dirty – please clean it.
10. The fan does not work – see the corresponding point.
11. There is a leak in the refrigeration cycle – please contact a BEKO service technician.
Reset the temperature switch by pressing the button on the temperature switch itself
– check the perfect functioning of the dryer.
The TS temperature switch is defective – replace it.
The
LED flashes because the dew point is too high – see the corresponding
point.
The
LED flashes because dew point is too low – see the corresponding point.
The
LED flashes because the sensor is defective or fails, the device indicates
the message "PF" (sensor failure), replace the sensor.
PNEUMATIG.EU - GDYNIA UL.WIELKOPOLSKA 158 -  58 622 49 22
Maintenance, troubleshooting, spare parts and dismantling
33

Hide quick links:

Advertisement

Table of Contents
loading