Interrogation Of Binary Information; Parameter Addresses For Function Code 05H - ABB PointMaster 200 Series Operating Manual

6-channel multipoint recorder, interface description
Table of Contents

Advertisement

Interrogation of binary information

(with telegram SD3 and function code 05H)
Is used to send a query to the recorder. The values transmitted
with function code 05 are not converted acc. to the numerical
format for analog values, since the information involved here is
exclusively binary information. The recorder uses one byte in the
answer message for each parameter address queried. Bits not
in use are set to 0 by the recorder.
The computer's query to the recorder is:
SD3/DA/SA/FC/aa/cc/xx/xx/xx/xx/xx/xx/FCS/ED
|<--
L

Parameter addresses for function code 05H

Parameter
Contents
address
00H
Threshold status, channel 1 to 4
01H
Threshold status, channel 5 and 6
02H
Status DI
03H
Status DO
04H
Equipment self-test status, bits 0...7
05H
Equipment self-test status, bits 8...15
06H
Equipment self-test status, bits
16...23
07H
Equipment self-test status, bits
24...31
08H
Parameterisation status
(01 = recorder is in parameterisation
mode, it is not possible to modify the
parameterisation via the interface)
The threshold status of channels 1 to 4 is stored in one byte:
Bit
7
Threshold 1 channel 1
6
Threshold 2 channel 1
5
Threshold 1 channel 2
4
Threshold 2 channel 2
3
Threshold 1 channel 3
2
Threshold 2 channel 3
1
Threshold 1 channel 4
0
Threshold 2 channel 4
The threshold status of channels 5 and 6 is stored in an additio-
nal byte:
30 Connection of the recorder to WIZCON
-->|
The following applies:
SD3
= A2H
Start byte
DA
Destination address (bus subscriber address)
SA
Source address
FC
= 05H
Function code
aa
Start address = Parameter address from section
„Parameter addresses"
cc
Number of data bytes
xx...
...xx
6 arbitrary bytes
FCS
Test byte (Frame Check Sequence)
Sum of the hex value of the L frame without transfor-
mation for FFH
ED
= 16H
End byte (End Delimiter), code: 16H
L
Number of bytes in FCS
The recorder's answer is:
SD2 LE LEr SD2 DA SA 05H Byte 1 Byte 2 ... Byte n FCS ED
Bit
..
3
Threshold 1 channel 5
2
Threshold 2 channel 5
1
Threshold 1 channel 6
0
Threshold 2 channel 6
The status of the binary inputs is stored in the lower 6 bits of a
byte:
Bit
..
5
DI 1 active
4
DI 2 active
3
DI 3 active
2
DI 4 active
1
DI 5 active
0
DI 6 active
The status of the binary outputs is stored in the lower 6 bits of a
byte:
Bit
..
5
DO 1 active
4
DO 2 active
3
DO 3 active
2
DO 4 active
1
DO 5 active
0
DO 6 active