INSTALLATION
WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED & YELLOW OUTPUT
LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN. DO NOT JOIN
INVERTER CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED TO
THE EMERGENCY BALLAST.
NOTE:
STEP #1
INSTALLING THE EMERGENCY BALLAST
> Disconnect AC power from the fixture. Remove the ballast channel cover and install the emergency ballast either
in the ballast channel or on top of the fixture.* Remote mounting distance must be less than half the maximum
remote mounting distance for the AC ballast. Consult AC ballast manufacturer before remote installation.
> Depending on the type of fixture in use install emergency ballast using one of the methods illustrated below.
INSIDE BALLAST CHANNEL
Inside Ballast Channel
* For installation on top of the fixture, wire bundle covers (RMC-60) may be required by state or local codes. These covers are
available from the manufacturer as an accessory kit and must be ordered separately. Call your local distributor or the factory for complete
information.
STEP #2
INSTALLING THE TEST SWITCH
> Refer to the illustrations above and install the test switch
through the ballast channel cover of a troffer or through the
side of a strip fixture.
> Drill a 1/2" hole and install the switch as shown.
> Refer to the diagrams below and wire the test switch so that
it removes AC power from both the emergency ballast and the
AC ballast at the same time.
UNSWITCHED FIxTURE
DOUBLE POLE
TEST SWITCH
BLK
BLK
HOT
RED
RED
COM
Make sure the necessary branch circuit wiring is available. An unswitched source of
power is required. The emergency ballast must be fed from the same branch circuit
as the AC ballast.
Inside Strip Fixture
INSIDE STRIP FIxTURE
BLACK
AC
BALLAST
WHITE
WHITE
EMERGENCY
BLACK 120V
BALLAST
OR
ORANGE 277V
(CAP UNUSED LEAD)
SWITCHED FIxTURE
DOUBLE POLE
TEST SWITCH
BLK
BLK
HOT
WALL
SWITCH
RED
RED
COM
2
On Top of Fixture
ON TOP OF FIxTURE
BLACK
AC
BALLAST
WHITE
WHITE
EMERGENCY
BLACK 120V
BALLAST
OR
ORANGE 277V
(CAP UNUSED LEAD)