Fleck 2510 Metered Flow Sensor Filter System Programming Guide

This is for Fleck 2510 backwash filters that have are equipped with the optional built-in flow sensor only.
There are two types of programming, standard USER PROGRAMMING, where you can set the time of day and
gallons of water used and/or days between backwashes. The second type is MASTER PROGRAMMING where
you can set the length of the backwash and rinse cycles, and make sure the control is set to the correct
settings for your type of MangOX filter:

User Programming

You can go into User Programming and make adjustments if you want to the flow meter setting or Day
Override setting. Use the User Programming to avoid having to go through the Master Programming for quick
changes to these settings below:
1.
Press the Up and Down buttons for five seconds while in service, and the time of day is NOT set to
12:01 PM.
2.
Day Override (Display Code DO): Set to 1 to 14 based on your particular filter system requirements.
Use the Up or Down arrows to change the setting. This is the critical setting that allows your filter to
backwash every fixed number of days. See your Installation and Start-up Guide for more information
or contact us for suggestions for this setting. Press the Extra Cycle button.
3.
Regeneration Time (Display Code RT): Set to 2:00 am generally or sometime when no water is being
used, and no other filter or softener is likely to be in a regeneration cycle. Press the Extra Cycle
button.
4.
Feed Water Hardness: Use this setting to adjust the feed water hardness. Set to 20 for most
applications. Press the Extra Cycle button. Note that actual 'Feed Water Hardness" is irrelevant to
filter systems, since hardness is being removed.
5.
Fixed Reserve Capacity (Display Code RC): Set to 0. No fixed reserve capacity is required for filters.
Press the Extra Cycle button.
6.
Press the Extra Cycle button to end User Programming Mode

Master Programming Mode (for Flow Sensor type)

Perform a Master Reset: Unplug the Fleck 2510 from the electrical wall outlet. Hold the Extra Cycle button
while plugging in and powering up the unit. This resets all of the parameters in the unit.