Addendum
NEW EN GRADE 3 FEATURES
Any Grade 3 Invincibell has an output on the PCB called 'FAULT', this is used to monitor the SAB back up
battery. This output does not need to wired to Grade 2 panels.
The Invincibell will do an active self test on the SAB back up battery every 24 hours. If the SAB back up
battery fails it's self test, then the FAULT relay will open and notify the control panel of a 'Warning Device
Fault'. It may then be necessary to replace the SAB back up battery.
The Invincibell siren trigger wire input must also be monitored to be compliant at Grade 3. On some control
panels it may be necessary to connect a resistor between the control panel siren output and 0V or 12V.
Refer to the full manual for Pyronix and Castle connections, for all other control panels please see the below
diagrams that show the Grade 3 connections on various manufacturers' control panels.
Note: If using 2 Grade 3 Invincibells please do not parallel the bell trigger wire. Always use a separate
output. Strobe trigger wires can be wired parallel.
When wiring an Aritech ATS 2003 3003 4003 the bell trigger wiring must be wired through a relay, as
shown in Figure A on page 2.
HONEYWELL
Input
(Programmed
as Fault)
OP Strobe
OP Bell
+
+12V
-
Tamper/Fault resistor values shown are 1K Alarm and 1K Tamper. These
values may change depending on the system programming.
SCANTRONIC 9600
STR
BELL
+12V
0V
TR
BACKLIGHT
DISABLE
T
T
ENG
HOLD
STB
BELL
+
12v
-
BACKLIGHT
DISABLE
T
T
ENG
HOLD
STB
BELL
+
12v
-
Bell Trigger Monitor Resistor (4K7):
Yellow, Violet Red
SCANTRONIC / COOPER
Input
(Programmed
as Fault)
NO
Strobe
C
NC
NO
Bell
C
NC
+
+12V
-
Tamper/Fault resistor values shown are 4K7 Alarm and 2K2 Tamper. These
values may change depending on the system programming.
SCANTRONIC 9651
STR
BELL
+12V
0V
TR
RINS1603-2
BACKLIGHT
DISABLE
T
T
ENG
HOLD
STB
BELL
+
12v
-
Bell Trigger Monitor Resistor (4K7)
Yellow, Violet Red
BACKLIGHT
DISABLE
T
T
ENG
HOLD
STB
BELL
+
12v
-
Bell Trigger Monitor Resistor (1K):
Brown, Black, Red

Advertisement

loading

Summary of Contents for Pyronix Invincibell Grade 3

  • Page 1 0V or 12V. Refer to the full manual for Pyronix and Castle connections, for all other control panels please see the below diagrams that show the Grade 3 connections on various manufacturers’ control panels.
  • Page 2 MENVIER ARITECH CD9503/CD15003 TRIG- BACKLIGHT BACKLIGHT DISABLE DISABLE STB- HOLD HOLD BELL BELL Bell Trigger Monitor Resistor (470Ω): Bell Trigger Monitor Resistor (4K7): Yellow, Violet, Brown Yellow, Violet Red ATS 2003 3003 4003 BACKLIGHT Tamper RTN DISABLE Input # HOLD BELL 12V 0V T NC C NO Figure A...
  • Page 3 Tamper/Fault resistor values shown are 4K7 Alarm and 2K2 Tamper. These Tamper/Fault resistor values shown are 6K8 Alarm and 4K7 Tamper. values may change depending on the system programming. These values may change depending on the system programming. PYRONIX (Pre-Version 9) GUARDALL PX48i Input BACKLIGHT...
  • Page 4: Control Panel

    INVINCIBELL BELL TRIGGER MONITORING INSTALLATION GUIDE MINIMUM BELL TRIGGER MONITORING VOLTAGE = 1.6 VOLTS MAXIMUM BELL TRIGGER MONITORING VOLTAGE = 3 VOLTS Step 1: Wire the Invincibell as shown in the Invincibell installation instructions, but leave the Bell Trigger wire disconnected. INVINCIBELL (GRADE 3) CONTROL PANEL Step 2:...
  • Page 5 Step 3: At the control panel measure the DC voltage between the 0 Volt Bell Hold off connection, and the Bell Trigger output connection. If the measured DC voltage is 12 Volts or above, then fit a 1K resistor between the 0 Volt Bell Hold off connection and the Bell Trigger output connection. Now move to STEP 4.
  • Page 6 Step 6: Close the Invincibell case lid and Tamper Switch and the Bell Trigger Monitoring will be fully operational. Step 7: If 0 Volts is measured when following instruction number 3, then ONLY fit a 4k7 resistor between the control panel +12 Volt Bell Hold off connection and the Bell Trigger output connection.