Connecting Units As Master/Slave

Connect the remote control pad to the unit designated as the Master unit as
described above (this unit will automatically detect it when powered up and
configure as the master). Units without a control pad will assume a salve status
when no room pad can be found.
Master and slave units should be connected via a Belden 9841 (or equivalent)
cable to the terminals labelled BACnet. Please daisy chain all positive terminals
together and all negatives together.
Do not connect units to a BMS network or another master/slave setup using this
configuration. Up to 10 slaves can be linked to a single master.