Measure Ionisation Current; Testing For Gas Leaks; Check The Operating Characteristics Of The Boiler; Final Steps - Bosch Worcester GB162-50 V2 Installation, Commissioning And Servicing Instructions

Commercial boiler series, wall hung gas fired condensing boiler for central heating systems and indirect fed domestic hot water
Table of Contents

Advertisement

Commissioning
8.10

Measure ionisation current

▶ Take the boiler out of operation.
▶ Pull the connector plugs apart.
▶ Connect the multi-meter on both sides of the open plugs (in series).
1.
2.
Fig. 73 Connecting the multi-meter
▶ Select the μA measurement value at the multi-meter.
▶ Bring the boiler into operation.
▶ Make sure that the boiler can dissipate the heat generated.
▶ Start the chimney sweep mode ( Chapter 7.3).
▶ Set the smallest possible output value in % (partial load).
▶ Measure the ionisation current.
The ionisation current must be at least 3 μA.
▶ If the value is lower, check the gas/air ratio and the
monitoring electrode.
▶ Enter the value in the maintenance protocol ( Chapter 11.15).
▶ Switch off the chimney sweep mode.
▶ Take the boiler out of operation.
▶ Remove the multi-meter.
▶ Re-connect the ionisation plugs.
▶ Bring the boiler into operation.
8.11

Testing for gas leaks

NOTICE: Damage to the boiler due to short-circuit.
▶ When using leak detection spray, cover the plug and
cables.
▶ Start the chimney sweep mode ( Chapter 7.3).
▶ As soon as the burner is on, check all gas-carrying components using
an approved gas leak detection spray.
36
▶ Check the rubber gasket [1] at the ignition unit and the monitoring
electrode for tightness.
Fig. 74 Inspecting the gas train
▶ Determine the cause of a possible leak.
▶ Take steps to remedy the leak.
▶ Exit the chimney sweep mode.
8.12
6 720 807 034-64.1DDC
▶ Create a heat demand and check whether the boiler starts burning
after several minutes to support the boiler operation.
▶ If applicable: open a DHW tap and check the DHW temperature and
DHW volume.
8.13
▶ Fit the casing.
▶ Complete the Benchmark checklist (50-V2 and 65-V2) or
commissioning report (85-V2 and 100-V2).
▶ Place second ID sticker [1] (part of the documentation set) at the
bottom right on the front cover.
Fig. 75 Second ID sticker
8.14
▶ Familiarise the user with the heating system and operation of the
boiler.
▶ Explain to the user how the heating system must be filled.
▶ Point out to the user that they must not carry out conversions, repairs
or maintenance themselves.
▶ Fill out the commissioning report to confirm commissioning
( Chapter 8.15).
▶ Hand the technical documentation to the user.
1

Check the operating characteristics of the boiler

Final steps

1

Inform the user

6 720 807 034-65.1DDC
6720814332-11.1TD
6720814332 (2018/04)