Flue Terminal Positions - Worcester Greenstar 8000 Life GR8300iW 30 R Installation And Maintenance Instructions Manual

Gas fired condensing regular boiler
Hide thumbs Also See for Greenstar 8000 Life GR8300iW 30 R:
Table of Contents

Advertisement

WARNING:
Minimum plume management length:
The minimum distance of 500mm must be maintained between air inlet
and exhaust.
▶ Do not terminate the plume management inside the terminal
exclusion zone (shaded area) shown in figure 28.
m
0 m
5 0
m m
5 0 0
Fig. 28 Terminal exclusion zone
NOTICE:
Cutting the 500mm pipe
▶ The Plume management extension kit contains the components
required for such a configuration.
4.4.4

Flue terminal positions

CAUTION:
Flue terminal positions
▶ All measurements are the minimum clearances required.
▶ Terminals must be positioned so to avoid combustion products
entering the building.
Greenstar 8000 Life – 6720883866 (2019/04)
5 0
0 m
m
±80°
0010013548-001