Equipment Selection Procedure - LG Mega LS090HEV2 Engineering Manual

Single zone mega and mega 115v wall mounted
Hide thumbs Also See for Mega LS090HEV2:
Table of Contents

Advertisement

Cooling / Heating Correction Factors
For Single Zone Mega Wall Mounted systems, calculate the equivalent length of the liquid line from the outdoor unit to the indoor unit. Also,
determine the elevation difference of the indoor unit above or below the outdoor unit. Find corresponding cooling or heating capacity correc-
tion factors as shown below. Multiply the correction factors by the cooling or heating capacity obtained from the capacity tables using design
conditions. The resultant is the NET cooling or heating capacity.
Cooling and Heating Capacity Coefficient
Table 31:
LS-090HEV2
Rate of
LS-120HEV2
Capacity
LS-180HEV2
Change (%)
LS-240HEV2
Table 32:
LS-090HXV
Rate of
Capacity
Change (%)
LS-180HXV
Equivalent Piping Length for Piping Components
Table 33: Equivalent Piping Length for Elbows.
Component
1/4
3/8
Elbow (ft.)
0.5
0.6
Altitude Correction Factor
The impact of air density must be considered on systems installed at a significant altitude above sea level, therefore, locally accepted alti-
tude correction factors using ASHRAE guidelines must be applied.

EQUIPMENT SELECTION PROCEDURE

Factors.
Operation
Mode
16.4
24.6
Cooling
100
100
Heating
100
100
Cooling
100
100
Heating
100
100
Operation
Mode
16.4
24.6
Cooling
100
100
Heating
100
100
Cooling
100
100
Heating
100
100
1/2
5/8
3/4
0.7
0.8
1.2
©
Piping Length (ft.)
32.8
49.2
65.6
82.0
97.7
93.0
-
-
98.3
95.0
-
-
99.0
97.0
95.0
-
99.2
97.6
96.0
-
Piping Length (ft.)
32.8
49.2
65.6
82.0
95.8
87.5
-
-
95.8
93.8
-
-
95.8
87.5
-
-
95.8
93.8
-
-
Size (Inches)
7/8
1
1-1/8
1-1/4
1.3
1.5
1.6
1.8
98.4
114.8
131.2
147.6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
98.4
114.8
131.2
147.6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1-3/8
1-1/2
1-5/8
1-3/4
2.0
2.1
2.3
2.5
PERFORMANCE DATA | 57