Electrical Data - LG Mega LS090HEV2 Engineering Manual

Single zone mega and mega 115v wall mounted
Hide thumbs Also See for Mega LS090HEV2:
Table of Contents

Advertisement

ELECTRICAL DATA

Electrical Data

Table 4: 208-230V, 60Hz, 1-Phase Single-Zone Mega System Electrical Data Table.
Nominal
Unit Model
Hertz Voltage
Tons
No.
3/4
LS090HEV2
1
LS120HEV2
60
208 - 230
1-1/2
LS180HEV2
2
LS240HEV2
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Table 5: 115V, 60Hz, 1-Phase Single Zone Single-Zone Mega 115V System Electrical Data Table.
Nominal
Unit Model
Hertz Voltage
Tons
No.
3/4
LS090HXV
60
1
LS120HXV
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
12 | PRODUCT DATA
Voltage Range
MCA
(Min. to Max.)
10.0
10.0
187-253
15.0
15.0
Voltage Range
MCA
(Min. to Max.)
13.5
115
104-127
13.5
©
Compressor Motor
Compressor
RLA
MOP
Quantity
Cooling
15
1
7.0
15
1
7.0
20
1
10.0
20
1
10.0
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.
Compressor Motor
Compressor
RLA
MOP
Quantity
Cooling
20
1
10.0
20
1
10.0
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.
Outdoor Fan Motor Indoor Fan Motor
Heating
W
FLA
7.0
43
0.4
7.0
43
0.4
10.0
85
0.4
10.0
85
0.4
Outdoor Fan Motor Indoor Fan Motor
Heating
W
FLA
10.0
43
0.4
10.0
43
0.4
W
FLA
30
0.4
30
0.4
58
0.4
58
0.4
W
FLA
30
0.5
30
0.5

Advertisement