GivEnergy 3600HY User Manual

Hybrid inverter

Advertisement

User Manual
Hybrid Inverter
(V1.00)
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 3600HY and is the answer not in the manual?

Questions and answers

Summary of Contents for GivEnergy 3600HY

  • Page 1 User Manual Hybrid Inverter (V1.00)
  • Page 2: Table Of Contents

    Contents 1 Notes on this manual ......................4 1.1 Validity ........................... 4 1.2 Target Group ........................ 4 1.3 Additional information ....................4 1.4 Storage of the manuals ....................4 1.5 Symbols Used ......................5 1.6 Markings on this product ..................... 6 2 Safety and conformity ......................
  • Page 3 10.2 Packing the Inverter ....................33 10.3 Storing the Inverter ....................33 10.4 Disposing of the Inverter ..................33 11 Operating Modes ........................ 34 12 Manufacturer Warranty ...................... 34 13 Technical Data ........................35 14.Contact ..........................37...
  • Page 4: Notes On This Manual

    1 Notes on this manual 1.1 Validity This manual describes the assembly, installation, commissioning and maintenance of the hybrid inverter. This manual does not cover any details concerning equipment connected to the unit ( e.g. PV modules). Information concerning the connected equipment is available from the manufacturer of the equipment.
  • Page 5: Symbols Used

    1.5 Symbols Used The following types of safety instructions and general information appear in this document as described below: Read the manual! Danger indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
  • Page 6: Markings On This Product

    1.6 Markings on this product Symbol description Warning regarding dangerous voltage The product works with high voltage. All work on the product must only be performed as described in its documentation. Beware of hot surface The product can become hot during operation. Do not touch the product during operation.
  • Page 7: Safety And Conformity

    2 Safety and conformity 2.1 Safety Instructions Danger to life due to lethal voltages! Lethal voltages are present within the unit and on the power supply lines. Therefore, only authorized electricians may install and open the unit. Even when the unit is disconnected, high contact voltages may still be present within the unit.
  • Page 8 Capacitive Discharge Currents PV modules with large capacities relative to earth, such as thin-film PV modules with cells on a metallic substrate, may only be used if their coupling capacity does not exceed 470nF. During feed-in operation, a leakage current flows from the cells to earth, the size of which depends on the manner in which the PV modules are installed (e.g.
  • Page 9: Product Description

    3 Product Description 3.1 Inverter Overview 3.2 Information of the unit The unit is bidirectional which applies to the PV system with battery storage. Energy produced by the PV system is used to optimize self-consumption; excess energy is used to charge the batteries, and then fed into the public grid when the PV energy is adequate, When PV energy output is insufficient to support connected loads, the system automatically get energy from the batteries if battery capacity is sufficient.
  • Page 10: Storage Of Inverter

    The inverter power flow direction indicator The inverter operation status indicator PV input terminals Battery input terminals and cover PV input switch WIFI com module and USB port BAT._NTC and RS485 communication (BMS com, load monitor com, ) AC Output terminals and cover Inverter Serial No.
  • Page 11: Unpacking

    carton is four. 4 Unpacking Thoroughly inspect the packaging upon received. If any damage to the carton is visible, or if you find that the unit is damaged after unpacking, please notify the shipping company immediately. Meanwhile please check the delivery for completeness and for visible external damage to the unit.
  • Page 12: Installation And Electrical Connection

    5 Installation and Electrical Connection 5.1 Safety Danger to life due to fire or explosion Despite careful construction, electrical devices can cause fires. Do not install the inverter on easily flammable materials and where flammable materials are stored. Risk of burns due to hot enclosure parts Mount the inverter in such a way that it cannot be touched inadvertently.
  • Page 13: Selecting The Installation Location

    Do not remove the casing until at least 5 minutes after disconnecting all power sources. Ø Although designed to meet all safety requirements, some parts and surfaces of Inverter are still hot during operation. To reduce the risk of injury, do not touch the heat sink at the back of the PV-Inverter or nearby surfaces while Inverter is operating.
  • Page 15 Ø The inverter can’t install to direct sunlight, direct heavy water sources or infirm locations. We suggest that the inverters should be installed at the location with some cover or protection。 Ø Observe the minimum clearances to walls, other inverters or objects as shown in the diagram below in order to guarantee sufficient heat dissipation.
  • Page 16 Ambient dimensions of one inverter Ambient dimensions of a series inverters Ø There must be sufficient clearance between the individual inverters to ensure that the cooling air of the adjacent inverter is not taken in. Ø If necessary, increase the clearance spaces and make sure there is enough fresh air supply to ensure sufficient cooling of the inverters.
  • Page 17: Mounting The Inverter With Bracket

    5.3 Mounting the Inverter with bracket In order to avoid electrical shock or other injury, inspect existing electronic or plumbing installations before drilling holes. Ø The dimension of bracket as follow: Ø Using the mounting frame as a template, drill holes as illustrated in image. Fix the mounting frame as the figure shows.
  • Page 18: Fixed The Inverter On The Wall

    5.4 Fixed the inverter on the wall Falling equipment can cause serious or even fatal injury, never mount the inverter on the bracket unless you are sure that the mounting frame is really firmly mounted on the wall after carefully checking. Ø...
  • Page 19: Check Inverter Installation Status

    Ø After confirming the inverter is fixed reliably, fasten four M6 safety-lock sockets head cap screws on the left and right side firmly to prevent the inverter from being lifted off the bracket. 5.5 Check Inverter Installation Status Ø Check the upper straps of inverter and ensure it fits on to the bracket. Ø...
  • Page 20: Electrical Connection

    5.6 Electrical Connection 5.6.1 Safety Danger to life due to lethal voltages! High voltages which may cause electric shocks are present in the conductive parts of the inverter. Prior to performing any work on the inverter, disconnect the inverter on the AC side, PV side, battery side.. Do not reverse input of battery! That will be destroyed the inverter! Danger of damage to electronic components due to electrostatic discharge.
  • Page 21 Position Description PV modules PV side breaker Inverter Main AC output breaker Energy meter Utility grid Battery Battery DC breaker Back-up output breaker(max.2500VA) Important load (max.2500VA) Load monitor Use only solid or stranded wire but not fine stranded wire. • Use cables with high ambient temperatures. •...
  • Page 22: Connecting To The Grid (Ac Utility)

    Code Name Detail Conductor cross-section See the Conductor cross section in the flowing chart Bare length 8mm around 5.6.3 Connecting to the grid (AC utility) Connecting to the grid. Output connection terminal...
  • Page 23 Current: the current much not less than 1.2 times of the inverter max output current which defined in the inverter spec. We suggest the AC separate unit spec as follow: Model 3600HY 4600HY 5000HY Ø Output cable requirements Product Model Area(mm²)
  • Page 24: Connect To Pv Panel

    Connecting to the back-up. The back-up can provide max output power 2500VA, you can connect the important load to the back-up terminal, however the on grid or the off grid , You must install an AC separate circuit-breaker or other load disconnection unit between the inverter back-up output and the important load, in order to ensure that the inverter can be safely disconnected under load.
  • Page 25 PV Input connection terminal There are two MPPT’s on the unit, so you can connect two independent MPPT channels. Ø Suggestions for the PV modules of the connected strings: Same type Same quantity of PV modules connected in series...
  • Page 26 Ø High voltages exist when the PV panel is exposed to the sun. To reduce risk of electric shock, avoid touching live components and treat connection terminals carefully Ø Cable requirements: Product Model Area(mm²) AWG No. 3600HY 5.26~9.0 8~10 4600HY 5.26~9.0 8~10 5000HY 5.26~9.0...
  • Page 27: Connect To The Battery

    5.6.5 connect to the battery Ø Before connecting to the battery, you much install a separate DC breaker (not less than 120A) between inverter and battery, that will ensure the inverter can be securely disconnected during maintenance. Reversed polarity will damage the inverter!!! Ø...
  • Page 28: Load Monitor Connect To The Inverter

    5, Screw the wire cable to the inverter’s battery input terminal. 6, If the inverter connects to the lithium battery, must connect the BMS to the BMS -RS485 communication port (we recommend using the GivEnergy appointed lithium battery, because the battery BMS communication meet the GivEnergy inverter.
  • Page 29 The CT installs direction as follow: The direction of the CT mark “K” arrow is point to the GRID! And the load monitor communication to the inverter via RS 485. Check the RS+ and RS- signal wiring is right! The load monitor input L-line much same as the CT sensor L-line, and the input of the load monitor L&N cannot reverse.
  • Page 30: The Inverter Parameter Setting

    7 Communications 7.1 WIFI The GivEnergy series of inverter use WIFI as standard wireless communication. Please read the WIFI module’s User Manual first, or visit our website for relative information. 7.2 the DRM0 function for SAA certification The DMR0 funtion of the GivEnergy series inverter provided for SAA.
  • Page 31: Start-Up And Shut Down The Inverter

    DRMO BAT_NTC BMS+ BMS- (RG/O) PIN5 PIN6 RS2+ RS2- RS1+ RS1- AR+ AR- Whenitreceives the order from DRM0 connection, the inverter will act responding to the order, the inverter must POWER OFF or POWER ON . 8 Start-Up and Shut Down of the inverter 8.1 Start-Up the inverter 1.
  • Page 32: Maintenance And Cleaning

    9 Maintenance and Cleaning 9.1 Checking Heat Dissipation If the inverter regularly reduces its output power due to high temperature, please improve the heat dissipation conditions. Maybe you need to clean the heat sink, or look for other obstructions. 9.2 Cleaning the Inverter If the inverter is dirty, shut down the inverter, then clean the enclosure lid.
  • Page 33: Packing The Inverter

    10.2 Packing the Inverter If possible, always pack the inverter in its original carton and secure it with tension belts. If it is no longer available, you can also use an equivalent carton. The box must be capable of being closed completely and made to support both the weight and the size of the inverter.
  • Page 34: Operating Modes

    Operating Modes The inverters have the following main Operating modes. 11 Manufacturer Warranty This certificate represents a 5 year warranty for the inverter products. Possession of this certificate validates a standard factory warranty of 5 years from the date of purchase, this must be registered online at www.insertwebhere.com...
  • Page 35: Technical Data

    12 Technical Data SPEC 3600HY 4600HY 5000HY Input Data (DC) Max. DC power 3800W 5000W 5400W Max. DC voltage 600V Start voltage 100V DC nominal voltage 360V PV voltage range 100V-600V MPP voltage range 120V-550V Max. input current per string...
  • Page 36 Max. charging/discharging 50A / 50A current Backup Output Output rate power 2500VA Peak power 3450VA,10s Output voltage 230Vac ±2%, 50Hz (60Hz Optional)±0.2%, THDV<3%(linear load) Efficiency Max. efficiency 97.10% 97.10% Euro - eta 96.50% 96.50% 96.50% MPPT efficiency 99.50% 99.50% 99.50% Protection Devices DC reverse polarity protection...
  • Page 37: Contact

    Note: Backup output power depends on the battery, Note: Specifications are subject to change without further notice. 14.Contact Please contact GivEnergy hotline if you need technical support, you may need to give us the following information: 1. Item No. of inverter 2.