Section 5
Troubleshooting
36
2
1
GUID-31DF5495-91F1-4A4B-8FD5-50625038961E V1 EN
Figure 3:
Testing a trip contact
1 Trip contact under test
2 Current limiting resistor
•
To check the status of the output circuits driving the output relay via the LHMI,
select Main menu/Monitoring/I/O status/Binary output modules and then
navigate to the board with the actual binary output to be checked.
•
Test and change the relay state manually.
1.
To set the IED to test mode, select Main menu/Test/IED test mode/
TestMode and set the parameter to "On".
2.
To operate or force the output relay to operate, select Main menu/Test/
Forcing/Binary output values and then navigate to the board with the
actual binary output relay to be operated/forced.
3.
Select the BOn_PO to be operated or forced and press
operate the actual output relay.
In PCM600, only the result of these operations can be checked by right-
clicking the product and selecting Signal Monitoring and then navigating to
A
V
1MRS756801 E
and
or
to
630 series
Commissioning Manual