Section 5
Troubleshooting
36
2
1
GUID-31DF5495-91F1-4A4B-8FD5-50625038961E V1 EN
Figure 3:
Testing a trip contact
1 Trip contact under test
2 Current limiting resistor
To check the status of the output circuits driving the output relay via the LHMI,
select Main menu/Monitoring/I/O status/Binary output modules and then
navigate to the board with the actual binary output to be checked.
Test and change the relay state manually.
1.
To set the IED to test mode, select Main menu/Test/IED test mode/
TestMode and set the parameter to "On".
2.
To operate or force the output relay to operate, select Main menu/Test/
Forcing/Binary output values and then navigate to the board with the
actual binary output relay to be operated/forced.
3.
Select the BOn_PO to be operated or forced and press
operate the actual output relay.
In PCM600, only the result of these operations can be checked by right-
clicking the product and selecting Signal Monitoring and then navigating to
A
V
1MRS756801 E
and
or
to
630 series
Commissioning Manual