Technical Specifications
Input Signal:
Output Signal:
Loss of Signal:
Connections:
Action:
Performance:
Flow Capacity:
Steady State
Consumption:
Power Gas Require-
ment:
Operative Temperature
Limits:
Housing:
Installation Orienta-
tion:
Approximate Weight: 15 pounds.
* Resolution and repeatability figures reflect a
positioner that is adjusted with a minimum dead-
band to reduce bleed gas. If the deadband is
eliminated (slightly increasing the bleed gas),
resolution and repeatability will improve.
HPP-5
Standard:
3-15 psi or 6-30 psi.
Adjustable: Zero is adjustable from 2-
30 psig, span is adjustable from 5-24
Pneumatic pressure as required by the
actuator up to full supply pressure.
Reverse Acting: Open on loss of signal.
Direct Acting: Close on loss of signal.
All Ports: ¼" N.P.T.
Direct and Reverse Acting:. Field-
reversible
Resolution:
0.4%*
Hysteresis: .6%*
C
= 1.5
V
Near Zero
Use clean, dry filtered (100 micron)
gas.
Discharging to Atmosphere:
150 psig maximum.
-20 to 160°F
(-28 to 70°C).
Meets NEMA 3 classification (weather
tight).
Vertical or horizontal position allow-
able.

Materials of Construction

Anodized 2024 Aluminum
External Parts:
316 Stainless Steel and 2024 Ano-
Internal Parts:
dized Aluminum
316 Stainless Steel
Feedback Lever:
Range Spring:
Plated Music Wire
Diaphragms:
Buna-N with Nylon Reinforcement
Seats and O-Rings:
Buna-N
Tubing:
316 Stainless Steel
316 Stainless Steel
Fittings:
Gauges:
2 ½" Dial Liquid filled Brass Con-
nection with Stainless Steel Case.
(Stainless Steel connection op-
Maximum Supply Regulator Capacity
Q = 312.86 x
P
1
=
Q
Min. Supply Regulators Capacity (scfh)
=
G
Specific Gravity of Gas
=
T
460 + Operative Temperature (°F)
Cv = Flow Factor
=
P
Supply Pressure to Positioner (psig)
1

Accessories

Atmospheric Bleed Control (AB Control):
maintains minimum pressure differential
across the cylinder. The AB Control is re-
quired in order to provide the necessary
output to operate the control valve under all
design conditions.
NBV No Bleed valve – same function as
DPS, no adjustments or tubing required.
Works up to 150 psig power gas.
DPS Series Non-Bleed Sensor: achieves
non-bleeding conditions in either full open
or full closed positions. Selection based
upon power gas pressure and discharge
gas pressure.
4
HPP-5 Positioner

Specifications

1
x C
x
(
V
× T
+
G
460
September 1999
)