14 Safe parameterisation - user responsibility

14.1 Safety-related configuration parameters

Parameters
CH1.FUN
CH2.FUN.
PASSW
The above safety-related configuration parameters are marked in red
text in the routing diagrams and must be verified by the user in a SIL-
configuration.

14.2 Verification procedure

The verification is done using the display / programming front PR 4501
by following the procedure described below.

14.2.1 if no password is set

action
1
Press OK
2
Set (ADV.SET) to Yes and press OK
3
Step down to (SIL SETUP) and press OK
4
Set (EN SIL) to YES and press OK
5
Set password to a number between 0 and
9999 and press OK
(At this time the module starts operating
in SIL mode with the entered configuration
parameters!)
6
Verify Channel 1 function and press OK
7
Verify Channel 2 function and press OK
8
Verify password and press OK
9
Verify SIL and press OK
* Open is shown briefly in the display.
8
9202 Pulse Isolator
Value
Description
DIR / INV
Direct / inverted channel function
DIR / INV
Direct / inverted channel function
0 - 9999
New password
Version No. V5R0
Display shows
ADV.SET
DISP SETUP
EN.SIL
NEW.PASS
VerifyOPEN
"briefly"
LOCK*
CH1.FUN
CH2:FUN
PASSW