Fm Installation Drawing - PR 9202 Series Manual

Pulse isolator
Table of Contents

Advertisement

Available languages

Available languages

LERBAKKEN 10, 8410 RØNDE DENMARK
For safe installation of 9202B the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
For Installation in Zone 2 / Division 2 the following must be observed.
The 4501 programming module is to be used solely with PR electronics modules. It is
important that the module is undamaged and has not been altered or modified in any way.
Only 4501 modules free of dust and moisture shall be installed.
c-FM-us Certificate
Hazardous area
Class I/II/III, Division 1, Group A,B,C,D,E,F,G
or Class I, Zone 0/1 Group IIC, [AEx ia] IIC or
or Class I, Zone 0/1 Group IIC, [Ex ia] IIC
Simple Apparatus or
Intrinsically safe apparatus
with entity parameters:
Vmax (Ui) ≥ Vt (Uo)
Imax (Ii) ≥ It (Io)
Pi ≥ Pt(Po)
Ca(Co) ≥ C
+ Ci
cable
La(Lo) ≥ L
+ Li
cable
U
/ Vt:
10.6 V
o
I
/ Isc:
12 mA
o
P
/P
:
32 mW
o
t
Lo/Ro La/Ra: 1150 H/
Group
IIC
IIB
Group
A,B
C,E,F
C
/C
2.0 F
6.0 F
o
a
L
/L
260 mH
780 mH
o.
a
Terminal CH1(44,42) CH2(54,52)
Revision date:
2011-11-20

FM Installation drawing

3034430
+
-
+
-
IIA
D,G
18 F
1000 mH
Version Revision
V4 R0
9202 - Product Version 9202-003
Non Hazardous area or
Class I, Division 2, Group A,B,C,D T4
or Class I, Zone 2 Group IIC T4
-20 ≤ Ta ≤ 60ºC
4501
CH1
44
43
42
41
54
CH2
53
52
51
9202
91 92 93 94 95
Power
Rail
U
: 253 V max. 400 Hz
m
Supply / Output
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
Prepared by:
PB
9202QF01
34
33
32
31
14
13
12
11
Page:
1/2
26

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

9202-0029202-003

Table of Contents