Revision 0.98 October 2017 UL 864 Compatibility Telefire's ADR-7000 product line complies with the requirements of several standards, including UL 864, IS 1220, EN 54, EN 12094, and GOST, and may comply with options or requirements of one of the standards and are not compliant with another standard.
(NACs) and three programmable dry contact Form C relays; 24Vdc outputs to devices that require additional 24Vdc supply are also included. Up to 32 ADR-7000 control panels can be networked in a single peer-to-peer network. Each control panel is capable to communicate with up to 16 RM-7000 digital annunciators via an RS-485 interface.
Figure 1 Typical ADR-7000 System SAVER-7000 and GUARD-7 Differences The SAVER-7000 is similar to the ADR-7000, but is stand-alone and can only have 2 loops and up to 3 RM-7000 remotes The GUARD-7 is a stand-alone control panel that is limited to 60 addresses and can only have 2 loops and up to 3 RM-7000 remotes –...
The ADR-7000’s main board can contain one to four ADR-7002 line cards, enabling control of as many as 508 addressable initiating devices, notification appliances and I/O modules. Each line card can be configured as a Class B or Class A loop.
Schematic ADR-7000 subassemblies Main Board – ADR-7021 The ADR-7000's ADR-7021 main board is designed for ease of installation and maintenance. Connectors are located in logical groups; on the left are the input from the power supply and battery connection; three dry contact relays; and a connector for changing the addresses of addressable modules.
Power Supply The ADR-7000 has a 150W power supply that accepts 110-240Vac (nominal) input. Zone Alarm Module – ADR-7000ZM The optional Zone Alarm Module may be installed in the ADR-7000 to visually indicate zones in alarm. Network Communication Module – LON-7000 The LON-7000 is a communication module that enables connection between control panels to establish a network.
2.6.1 Topology An ADR-7000 LonWorks network can connect from 2 and up to as many as 32 ADR-7000 control panels in a peer-to-peer or Master-slave network. The physical topology of the network may be bus (figure 8), ring (figure 9) or free (figure 10) topology.
Remote Annunciator – RM-7000 The RM-7000 Remote Panel and Annunciator enables control and supervision of the ADR-7000 fire alarm control panel from remote locations and key positions such as security officer, premises manager, or maintenance office. The RM-7000 remote panel consists of an LCD display, keyboard, internal buzzer, and features such as alarm output, trouble output, and an interface relay that reduces the need for additional input/output interface modules.
Stopping the flashing of the LEDs in the general alarm area and turning them solid on (UL version only) Supervisory State Screen 5 Supervisory state The ADR-7000 has a supervisory function that conforms to UL and EN standards. – Page 12 of 87 –...
UL Models UL 864 For UL models of the ADR-7000, pressing the Acknowledge key stops the flashing of the LEDs in the general alarm area, in the LCD display and clarification area and the private LEDs in the zones and turning them solid on.
Cable Planning – SLC (Loop) Cable 4.2.1 The ADR-7000 allows wiring of the SLC loop in a closed loop (NFPA Style 6 Class A) as well as branching T-shaped (NFPA Style 4 Class B) wiring configuration. – Page 17 of 87 –...
Page 24
Use up to 20 LI-3000 line isolators per SLC loop. Note Class A is defined per line card in the ADR-7000. In a control panel that has more than one line card, it is possible to have some of the line cards working in Class A, and the others working in Class B.
Page 25
Cable Planning – LON-7000 Galvanic Networks 4.2.7 It is possible to extend the ADR-7000's capacity by networking two or more (as many as 32) control panels in a Master/Slave or Peer-to-Peer network. In order to maximize the distance between ADR-7000 control panels interconnected in a LonWorks network use a twisted pair cable of the types described in the following table.
Page 26
Use two-wire cables (twisted-pair is recommended) 18 to 12 AWG (cross section of 0.8 to 3.3 mm Two pairs from the ADR-7000 to the TFP-3000 – one pair for 24Vdc supply and one pair for SLC communication. 4.2.10 Pre-Installation Planning – Current Consumption and Battery...
Avoid exposure to severe conditions such as high humidity, dust and air pollution. The ADR-7000 should be mounted on a solid wall in order to allow easy access for installation, daily operations and maintenance. The cabinet should be mounted by using the two sliding slots on the upper back part of it and a screw hole on the lower part.
During the first power on you will be asked to key in an activation code. This 8 digit is unique to each control panel. You can get the code with a mobile phone application Telefire Reg7 that is available in Google Play app store for Android phones, or with a phone call to 03 970 0444.
1 minutes between one minute to 239 minutes, or constant (that is, it will stay on until the control panel is reset). EN 12094 Requirement EN 12094 See section 14.6 on page 87 for ADR-7000 EN 12094-1 compliance. UL 864 UL Requirement UL 864 paragraph 36.1.7 states that "An automatic delay provided prior to...
A password is required to respond from the panel keys. The ADR-7000's user interface panel is divided into three parts: The leftmost part has four keys to silence and resound alarms, perform practice drills, silence the buzzer, and reset the control panel. Below these keys in a space for optional zone display LEDs.
Revision 0.98 October 2017 UL 864 paragraph 59.1 Compliance The ADR-7000 product family is UL 864 complaint, and does not allow setting that contradict the standard's requirements. The following products mentioned in this manual were not tested or listed by UL and should not be installed where UL listing is required: ...
Note Telefire's ADR-7000 product line complies with the requirements of several standards, including UL 864, IS 1220, EN 54, EN 12094, and GOST, and may comply with options or requirements of one of the standards and are not compliant with another standard.
Page 61
8.9.2 Main Screen Message This option allows to change the message that is displayed under the Telefire logo. You can key in up to 24 characters to indicate the service company name or phone number. Use the arrow keys to select each character and Enter to key it in. Quit and save to keep the new message.
Periodic Tests Periodic maintenance shall be, as a minimum, performed per NFPA 72. Maintenance shall be performed by a trained or authorized Telefire representative. The system should be inspected entirely at least twice a year, or as required by national and/or local fire codes.
TPS-74A and TPS-34A auxiliary power supplies 12.3 UL Listing UL Certification Please note that the ADR-7000 was certified to UL 864 with the following devices: TFO-480A and TFO-440A Photoelectric Smoke Detectors ADR-705 and ADR-805A Addressable Switch Input ADR-712 and ADR-718 Input Modules ...
9,999 alarms / 9,999 faults Drift compensation update time ........3 hours 13.2 Power Supply The ADR-7000 contains a 150W power supply. The SAVER-7000 and GUARD-7 contain a 100W power supply. Battery charging ............automatic, variable current automatically controlled. Max charging current 1,500mA ±10%...
Power Requirement – Final Calculation Table 5 The ADR-7000’s power supply module can charge batteries in capacity of up to 12AH. The battery enclosure can contain two 12V sealed lead-acid batteries, up to 20 (W) by 7 (D) by 12 (H) cm each.
UL 864 Compliance UL 864 Compliance The ADR-7000 is a UL 864 compliant system that can be used as a standard fire detection and alarm system including sprinkler supervision; fire detection and extinguishing release system; fireman phone system; a compliant smoke control.
14.6 EN 12094-1 Compliance EN 12094 Compliance EN 12094 The ADR-7000 complies with EN 12094-1 mandatory functions and the following options with requirements: Section 4.17: Delay of extinguishing signal Section 4.18: Signal representing the flow of extinguishing agent Section 4.19: Monitoring of the status of components Section 4.20: Emergency hold device...