Telefire ADR-7000 Technical Manual

Telefire ADR-7000 Technical Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

T
F
& G
D
ELEFIRE
IRE
AS
ETECTORS
PO Box 7036
Petach Tikva 49250
Israel
Tel:
972 3 970 0400
Fax:
972 3 921 1816
eMail:
info@telefire.com
Web:
www.telefire.com
ADR-7000 / SAVER-7000 /
Fire Alarm Control Panel
L
TD
GUARD-7
Addressable
Technical Manual
ADR-7000En 98.pdf
Revision 0.98
October 2017

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ADR-7000 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Telefire ADR-7000

  • Page 1 ADR-7000 / SAVER-7000 / GUARD-7 Addressable Fire Alarm Control Panel Technical Manual & G ELEFIRE ETECTORS PO Box 7036 Petach Tikva 49250 ADR-7000En 98.pdf Israel Tel: 972 3 970 0400 Fax: 972 3 921 1816 Revision 0.98 eMail: info@telefire.com October 2017 Web: www.telefire.com...
  • Page 2 The terms “Trouble” as used in NFPA 72 guideline and UL standards and “Fault” as used in EN 54 standards are used interchangeably throughout this manual. Note Do not install, operate, and maintain this ADR-7000 before fully reading this manual. © 2017 – 2017 Telefire Fire & Gas Detectors Ltd.
  • Page 3: Table Of Contents

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Table of Contents INTRODUCTION .................... 1 SAVER-7000 GUARD-7 D ........... 2 IFFERENCES ADR-7000 CONTROL PANELS ..............3 – ADR-7021 ................4 OARD –...
  • Page 4 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 DISPLAY AND KEYBOARD ................ 33 LCD D ....................33 ISPLAY ......................34 ..................36 PERATOR ..............37 UMERICAL AND RROW SYSTEM CONFIGURATION (PROGRAMMING) PROCESS ...... 38 ..................
  • Page 5 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 10 PERIODIC TESTS ..................74 – D 10.1 ..........74 EEKLY ONE BY UPERVISOR 10.2 ..................... 74 ATTERY 11 WARNINGS AND LIMITATIONS ..............75 12 COMPATIBILITY ..................
  • Page 6: Adr-7000 / Saver

    Revision 0.98 October 2017 UL 864 Compatibility Telefire's ADR-7000 product line complies with the requirements of several standards, including UL 864, IS 1220, EN 54, EN 12094, and GOST, and may comply with options or requirements of one of the standards and are not compliant with another standard.
  • Page 7: Introduction

    (NACs) and three programmable dry contact Form C relays; 24Vdc outputs to devices that require additional 24Vdc supply are also included. Up to 32 ADR-7000 control panels can be networked in a single peer-to-peer network. Each control panel is capable to communicate with up to 16 RM-7000 digital annunciators via an RS-485 interface.
  • Page 8: Saver-7000 And Guard-7 Differences

    Figure 1 Typical ADR-7000 System SAVER-7000 and GUARD-7 Differences The SAVER-7000 is similar to the ADR-7000, but is stand-alone and can only have 2 loops and up to 3 RM-7000 remotes The GUARD-7 is a stand-alone control panel that is limited to 60 addresses and can only have 2 loops and up to 3 RM-7000 remotes –...
  • Page 9: Adr-7000 Control Panels

    The ADR-7000’s main board can contain one to four ADR-7002 line cards, enabling control of as many as 508 addressable initiating devices, notification appliances and I/O modules. Each line card can be configured as a Class B or Class A loop.
  • Page 10: Main Board - Adr-7021

    Schematic ADR-7000 subassemblies Main Board – ADR-7021 The ADR-7000's ADR-7021 main board is designed for ease of installation and maintenance. Connectors are located in logical groups; on the left are the input from the power supply and battery connection; three dry contact relays; and a connector for changing the addresses of addressable modules.
  • Page 11: Keyboard And Display Module - Adr-7003

    Power Supply The ADR-7000 has a 150W power supply that accepts 110-240Vac (nominal) input. Zone Alarm Module – ADR-7000ZM The optional Zone Alarm Module may be installed in the ADR-7000 to visually indicate zones in alarm. Network Communication Module – LON-7000 The LON-7000 is a communication module that enables connection between control panels to establish a network.
  • Page 12: Tcp/Ip Module - Net-7000

    2.6.1 Topology An ADR-7000 LonWorks network can connect from 2 and up to as many as 32 ADR-7000 control panels in a peer-to-peer or Master-slave network. The physical topology of the network may be bus (figure 8), ring (figure 9) or free (figure 10) topology.
  • Page 13: Loop Expansion Card - Adr-7001Em1 - Adr-7000 Only

    Remote Annunciator – RM-7000 The RM-7000 Remote Panel and Annunciator enables control and supervision of the ADR-7000 fire alarm control panel from remote locations and key positions such as security officer, premises manager, or maintenance office. The RM-7000 remote panel consists of an LCD display, keyboard, internal buzzer, and features such as alarm output, trouble output, and an interface relay that reduces the need for additional input/output interface modules.
  • Page 14: Access Levels

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 2.10 Access Levels The control panel allows protection from unauthorized access through protection of certain functions by various access levels. The control panel includes an electronic locking mechanism that allows work in 4 access levels: ...
  • Page 15 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Users 2 Users 4 and Action User 1 User 6 and 3 Senior Guard Operator Programmer Programmer   Device programming ...
  • Page 16: Work States - Alarm, Fault, Supervisory, Disablement, And Test Modes

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Work States – Alarm, Fault, Supervisory, Disablement, and Test Modes Alarm, fault or supervisory events are shown clearly by dedicated LEDs that are labeled Fire, Fault, and Supervisory, respectively.
  • Page 17: Revision 0.98 October

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 In case only one alarm triggered the alarm verification clock, during and up to 120 seconds, no additional alarm is received, the clock will be reset and the control panel will be back in normal mode.
  • Page 18: Fault State

    Stopping the flashing of the LEDs in the general alarm area and turning them solid on (UL version only) Supervisory State Screen 5 Supervisory state The ADR-7000 has a supervisory function that conforms to UL and EN standards. – Page 12 of 87 –...
  • Page 19: Disablement State

    UL Models UL 864 For UL models of the ADR-7000, pressing the Acknowledge key stops the flashing of the LEDs in the general alarm area, in the LCD display and clarification area and the private LEDs in the zones and turning them solid on.
  • Page 20: Test State

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Test State Screen 7 Test state Test state allows testing the control panel without activating outputs. This state is indicated by the Test LED.
  • Page 21: Installation

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Installation The planning process should take into consideration the entire system. Start by going over the project plans and determine the quantity and location of various detectors, call points, sounders, strobes, and other fire-safety devices as required.
  • Page 22 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Description Multiply by Addresses ADR-705 Dual Switch Interface Module configured as a single address ADR-705 Dual Switch Interface Module configured as two addresses...
  • Page 23: Cable Planning

    Cable Planning – SLC (Loop) Cable 4.2.1 The ADR-7000 allows wiring of the SLC loop in a closed loop (NFPA Style 6 Class A) as well as branching T-shaped (NFPA Style 4 Class B) wiring configuration. – Page 17 of 87 –...
  • Page 24 Use up to 20 LI-3000 line isolators per SLC loop. Note Class A is defined per line card in the ADR-7000. In a control panel that has more than one line card, it is possible to have some of the line cards working in Class A, and the others working in Class B.
  • Page 25 Cable Planning – LON-7000 Galvanic Networks 4.2.7 It is possible to extend the ADR-7000's capacity by networking two or more (as many as 32) control panels in a Master/Slave or Peer-to-Peer network. In order to maximize the distance between ADR-7000 control panels interconnected in a LonWorks network use a twisted pair cable of the types described in the following table.
  • Page 26 Use two-wire cables (twisted-pair is recommended) 18 to 12 AWG (cross section of 0.8 to 3.3 mm Two pairs from the ADR-7000 to the TFP-3000 – one pair for 24Vdc supply and one pair for SLC communication. 4.2.10 Pre-Installation Planning – Current Consumption and Battery...
  • Page 27: Wiring

    Avoid exposure to severe conditions such as high humidity, dust and air pollution. The ADR-7000 should be mounted on a solid wall in order to allow easy access for installation, daily operations and maintenance. The cabinet should be mounted by using the two sliding slots on the upper back part of it and a screw hole on the lower part.
  • Page 28 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Figure 4 Mounting holes in the Chassis – Page 22 of 87 –...
  • Page 29 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Figure 5 Mounting Figure 6 Flush Mounting The wiring opening on the top right of the cabinet should be covered with a metal sheet.
  • Page 30 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Note All power-limited circuit wiring must be at least 0.25" (6.35mm) away from any non power-limited circuit wiring. Use different entries of the cabinet or conduits.
  • Page 31 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Connection diagram – GUARD-7 Figure 9 4.4.3 Testing the SLC Loops Resistance measurements: Short the end of one branch and measure the resistance from the connections of the loop to the control panel.
  • Page 32 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Figure 12 Example connection – detectors Figure 13 ADR-7000 cable routing 4.4.4 Connecting Low-Voltage Devices Warning Measure the wiring to ensure there are no shorts or ground faults prior to connecting field cabling to the control panel.
  • Page 33 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Warning Do not connect extinguishing devices at this time. Use a dummy load to test. 4.4.5 Connecting AC Power Connect the control panel’s AC input line to a dedicated circuit breaker that is not shared by other appliances or equipment.
  • Page 34: Post-Installation

    During the first power on you will be asked to key in an activation code. This 8 digit is unique to each control panel. You can get the code with a mobile phone application Telefire Reg7 that is available in Google Play app store for Android phones, or with a phone call to 03 970 0444.
  • Page 35 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Warning Forgotten passwords require factory reset: if you lose or forget the password, the panel must be sent back to the factory to be reset. There is no field option for gaining access to the panel without a valid password.
  • Page 36: Automatic Extinguishing

    1 minutes between one minute to 239 minutes, or constant (that is, it will stay on until the control panel is reset). EN 12094 Requirement EN 12094 See section 14.6 on page 87 for ADR-7000 EN 12094-1 compliance. UL 864 UL Requirement UL 864 paragraph 36.1.7 states that "An automatic delay provided prior to...
  • Page 37: Extinguishing Disconnect

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 The Control panel supports fire extinguishing Hold (EN 12094) / Abort (UL 864) buttons. A device defined as a fire extinguishing Hold (EN 12094) / Abort (UL 864) button delays fire extinguishing activation as long as the button is pressed.
  • Page 38 Warning Connect only extinguishing devices that are authorized by Telefire and the authority having jurisdiction. – Page 32 of 87 –...
  • Page 39: Display And Keyboard

    A password is required to respond from the panel keys. The ADR-7000's user interface panel is divided into three parts: The leftmost part has four keys to silence and resound alarms, perform practice drills, silence the buzzer, and reset the control panel. Below these keys in a space for optional zone display LEDs.
  • Page 40: Leds

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 LEDs Meaning Power Green LED. Indicates the presence of input power (AC or battery).  Always on in normal operation  Flashes when there is no main power until Acknowledge key is depressed.
  • Page 41 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Meaning Aux 24V Fault Yellow LED. Indicates a fault in the auxiliary 24Vdc outputs. Additional detail is shown on the LCD display.
  • Page 42: Operator Keys

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Meaning Telecom Active Yellow LED. Indicates a fault event in the dialer line. Additionally a fault alert marks this event.  Off in normal operation ...
  • Page 43: Numerical And Arrow Keys

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Function Buzzer Off Pressing this key silences only internal buzzer.  In normal mode – used to scan through the existing events.
  • Page 44: System Configuration (Programming) Process

    © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 System Configuration (Programming) Process The ADR-7000's site-specific data can be programmed and modified on site to respond to each site's specific requirements. ADR-3000 programming requires level 3 access.
  • Page 45: Entering Configuration State

    Revision 0.98 October 2017 UL 864 paragraph 59.1 Compliance The ADR-7000 product family is UL 864 complaint, and does not allow setting that contradict the standard's requirements. The following products mentioned in this manual were not tested or listed by UL and should not be installed where UL listing is required: ...
  • Page 46 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 UL Requirement UL 864 UL 864 paragraph 36.1.7 states that "An automatic delay provided prior to release operation by a system shall be a maximum of 60 seconds, timed from...
  • Page 47: System Configuration (Programming)

    Note Telefire's ADR-7000 product line complies with the requirements of several standards, including UL 864, IS 1220, EN 54, EN 12094, and GOST, and may comply with options or requirements of one of the standards and are not compliant with another standard.
  • Page 48: Enablement / Disablement

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Screen 11 Main Menu (1 of 2) Enablement / Disablement 8.2.1 Enabling and Disabling a Device This function is used for temporary disabling a device. A disabled device shall not cause any fault (with the exception of a Disablement notification);...
  • Page 49 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017  Switch (select All Modes; Reset Switch; Silence; Disconnect; Supervisory; Abort; Release; Alarm Matrix; or Fan FC)  Power Supply  Sounder ...
  • Page 50: Monitor

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Screen 16 Enable / Disable Main Board Outputs This operation allows the disablement or enablement of main board outputs (Alarm Dialer; FWRE Dialer; NAC 1; NAC 2; Relay 1; Relay 2; or Relay 3), rather than a physical loop.
  • Page 51 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 8.4.1 Alarms System reports detail the number of alarms, faults, devices under test, key operations, device list, active outputs and preventive maintenance recommendations.
  • Page 52 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 8.4.3 Field Test Screen 24 System reports – walk test (panel selection) Screen 25 System reports – individual walk test 8.4.4 Key Operations Screen 26 System reports –...
  • Page 53 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 8.4.5 Device Listing Screen 28 System reports – device report Device List report allows you to check device quantities. You can check all loops, a specific loop, and either all devices or a specific device type, such as heat detector r sounder.
  • Page 54: Utilities

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Utilities 8.5.1 Lamp Test Lamp test turns on all LEDs in the keyboard / display and activates the internal buzzers for a few seconds.
  • Page 55 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 The keyboard can be configured to auto-lock continuously, 10 minutes, 30 minutes, or one hour after last use. IS 1220 Requirement IS 1220 IS 1220 requires that auto lock timeout shall not exceed 30 minutes.
  • Page 56 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017  Night – Continuous operation in night mode (without automatic change).  Time-Related – Automatic shifting from Day to Night mode and vice versa, according to time settings.
  • Page 57: Walk Test

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 3V Battery: battery voltage (this battery is used for configuration back up when the control panel is powered off) 10. Total current: total current from all 24Vdc outputs; both NACs and all loops 11.
  • Page 58 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Screen 36 Walk test – main screen 8.6.2 View Progress Selection option 2 View Progress shall show the total number of devices tested.
  • Page 59: System View

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 System View 8.7.1 Licensing Screen 39 System view – panel licensing See section 4.5.1 on page 28 for explanation about panel registration.
  • Page 60: Smoke Control Test

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Smoke Control Test Screen 43 Smoke control test Screen 44 Smoke control test – test progress Screen 45 Smoke control test – test report...
  • Page 61 8.9.2 Main Screen Message This option allows to change the message that is displayed under the Telefire logo. You can key in up to 24 characters to indicate the service company name or phone number. Use the arrow keys to select each character and Enter to key it in. Quit and save to keep the new message.
  • Page 62 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 8.9.5 SLC Loops You can define each loop as active or inactive (Active: No), or working in either Class B or Class A. You can also see the number of loops defined in the panel.
  • Page 63 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Screen 53 System configuration – NAC output 8.9.9 Relays This menu allows you to configure the operation of the main board's 3 relays. You can select between Alarm, Supervisory, Fault, and Pre-Alarm.
  • Page 64 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 8.9.12 Remote Displays This menu configures the RM-7000 remote anunciators. You can select whether each of the 16 RM-7000 is active or not; Class A or Class B wiring; and assign a 19 character description to each RM-7000.
  • Page 65: Addressable

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Screen 60 System configuration – loop expansion card 8.9.16 Ground Fault This menu allows you to change the control panel's sensitivity to ground faults, or disable it completely.
  • Page 66 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Screen 63 System configuration – first fault delay UL Requirement UL 864 compliance requires this value to be less than 180 seconds.
  • Page 67: Device Program

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Screen 65 System configuration – communication with ADR-3000 8.9.21 Smoke Control Allows to set the day and time of weekly Smoke Control system test.
  • Page 68: Addressable

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017  Device Type: the device type as follows:  Photoelectric Detector: (TFO-480A or TFO-440A)  Heat Detector: (TFH-280A or TFH-220A). Detector mode (Fixed Temperature (default) or Rate of Rise) is defined in the Mode field.
  • Page 69 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017  For switches: Alarm; Reset; Silence; Disconnect; Supervisory; Abort; Release; Alarm Matrix; or Fan PC  For sounder / strobe: whether this NAC works as the protocol that is defined in the control panel or without protocol.
  • Page 70: Creating Device Groups

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Screen 69 Automatic device programming Screen 70 Automatic device programming – completion message 8.11 Creating Device Groups Device groups are intended to assign the same entity to several devices without restrictions of loop, address, or zone in order to perform a single operation such as disablement in one step.
  • Page 71: Change Passwords

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Screen 73 Clear reports 8.14 Change Passwords This menu option allows you to change passwords. There are three IDs for Operator (EN 54 access level 2) passwords, and three IDs of Programmer (EN 54 access level 3) passwords.
  • Page 72 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Pressing Enter will activate the fast Initializing. The system will display the message "DONE!" upon completion. Pressing the Quit key exits this window without performing the fast update.
  • Page 73: Troubleshooting

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Troubleshooting LEDs 9.1.1 LEDs on the User Display See section 6.2 on page 34 for an explanation of LEDs. 9.1.2 LEDs on the Main Board The red LED light next to the battery connector on the main card turns on when the charger charges the batteries.
  • Page 74 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Error Messages Possible Cause Repair Action Main circuit <device> "-" There is a negative line to Find the source of the fault –damaged wire or a water...
  • Page 75: Addressable Device Faults

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Addressable Device Faults Error Messages Possible Cause Repair Action Find the source of the fault – <address> "-" There is a negative line to...
  • Page 76 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Error Messages Possible Cause Repair Action <address> sirens circuit The siren circuit is Reconnect is disconnected disconnected at the extinguishing controller <address> output...
  • Page 77: Programming Faults

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Programming Faults Error Messages Possible Cause Repair Action <address> exists, not There is a device attached to Program the device in, open...
  • Page 78 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Error Messages Possible Cause Repair Action The area matrix includes This message will be Reactivate the disabled a region that was received when a region's...
  • Page 79: Status Messages

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Status Messages These messages show a system status such as a phone call on a fireman phone system or Extinguishing Abort or Extinguishing Hold in progrees. Information only – no need for any action.
  • Page 80: Periodic Tests

    Periodic Tests Periodic maintenance shall be, as a minimum, performed per NFPA 72. Maintenance shall be performed by a trained or authorized Telefire representative. The system should be inspected entirely at least twice a year, or as required by national and/or local fire codes.
  • Page 81: Warnings And Limitations

    ADR-7000 and/or resulting from its inaction.
  • Page 82: Compatibility

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Compatibility The ADR-7000 control panel is compatible with all of the following devices: 12.1 Input Devices 12.1.1 Direct Attachment to the SLC Loop ...
  • Page 83: Ul Listing

    TPS-74A and TPS-34A auxiliary power supplies 12.3 UL Listing UL Certification Please note that the ADR-7000 was certified to UL 864 with the following devices:  TFO-480A and TFO-440A Photoelectric Smoke Detectors  ADR-705 and ADR-805A Addressable Switch Input  ADR-712 and ADR-718 Input Modules ...
  • Page 84: Specification

    9,999 alarms / 9,999 faults Drift compensation update time ........3 hours 13.2 Power Supply The ADR-7000 contains a 150W power supply. The SAVER-7000 and GUARD-7 contain a 100W power supply. Battery charging ............automatic, variable current automatically controlled. Max charging current 1,500mA ±10%...
  • Page 85: Main Board - Relays

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 NAC 2 – See NAC 1 unavailable for SAVER-7000 SLC card 1 NFPA classification: Class B (NFPA style 4) or Class A (NFPA style 6 or 7) Class B or Class A is configurable at single loop level current protection ...........
  • Page 86: Certification

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Certification Telefire’s ADR-7000 Addressable Control Panels have the following approvals:  EN 54 Approved  UL 864 Edition 10 Listed  GOST Approved ...
  • Page 87: Appendix A - Current Consumption And Battery Capacity Calculation

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Appendix A – Current Consumption and Battery Capacity Calculation Repeat this process separately for each control panel. Fill in the following table to calculate the total load on the system’s power supply during quiescence (standby) state and alarm.
  • Page 88 ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 At least one and no more than two line cards (ADR-3002 and ADR-3002C) of any combination can be installed in the ADR-7000.
  • Page 89: Fire Alarm Control Panel

    Power Requirement – Final Calculation Table 5 The ADR-7000’s power supply module can charge batteries in capacity of up to 12AH. The battery enclosure can contain two 12V sealed lead-acid batteries, up to 20 (W) by 7 (D) by 12 (H) cm each.
  • Page 90: When Are Auxiliary Power Supplies Needed

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Note TPS-34A Addressable Auxiliary Power Supplies should be installed as close as possible to the devices they provide power to in order to reduce power loss.
  • Page 91: Appendix B - Detector Sensitivity Selection

    ADR-7000 / SAVER-7000 / GUARD-7 © 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017 Appendix B – Detector Sensitivity Selection 14.1 Smoke Detector Sensitivity Settings Least Night Most Sensitivity Sensitive Default Default Sensitive Obscuration (% per foot)
  • Page 92: Appendix C - Standards Compliance

    UL 864 Compliance UL 864 Compliance The ADR-7000 is a UL 864 compliant system that can be used as a standard fire detection and alarm system including sprinkler supervision; fire detection and extinguishing release system; fireman phone system; a compliant smoke control.
  • Page 93: En 12094-1 Compliance

    14.6 EN 12094-1 Compliance EN 12094 Compliance EN 12094 The ADR-7000 complies with EN 12094-1 mandatory functions and the following options with requirements: Section 4.17: Delay of extinguishing signal Section 4.18: Signal representing the flow of extinguishing agent Section 4.19: Monitoring of the status of components Section 4.20: Emergency hold device...