Contents subject to change. ELTHERM GmbH accepts no liability for any errors in this documentation.. No liability whatsoever will be accepted for damage incurred in direct connection with the supply or use of this documentation, unless there is a legal obligation.
BU-020 Operating Instructions for Temperature Controller ELT-GP1 Revision 4 20.12.2018 Product Description Function In control and monitoring mode, the unit regulates connected heaters to a given set-point (i.e. target temperature). Monitoring is done based on preset temperature limits. If a limit is exceeded or is not reached, potential-free contacts are switched (K3).
BU-020 Operating Instructions for Temperature Controller ELT-GP1 Revision 4 20.12.2018 Technical Data Mains voltage: 230 V, 50 Hz Power consumption: max. 5 VA Temperature measuring -51°C to +870°C range: Controller range: 0°C to 200°C (standard configuration) Hysteresis Accuracy: with Pt100: ±(0.5°C+0.5% of meas.r.)
BU-020 Operating Instructions for Temperature Controller ELT-GP1 Revision 4 20.12.2018 Terminals: Explanation Terminal No. Name Meaning Mains connection for the unit (phase conductor). Second "L" terminal. Possible use: The heater is to be connected directly to the unit. In this case: Jumper from 2 to 7.
BU-020 Operating Instructions for Temperature Controller ELT-GP1 Revision 4 20.12.2018 General Safety Instructions Proper use In its standard configuration, the temperature controller ELT-GP 2 is a two-position controller used to control electric heaters. The controller also indicates temperature deviations of the heater and any faults which may occur in the temperature probes used for this purpose.
BU-020 Operating Instructions for Temperature Controller ELT-GP1 Revision 4 20.12.2018 Installation Mounting The housing is designed for wall mounting. Drill four holes, ∅ 4 mm, using the mounting template. Attach housing with screws (not included). Glands are directed downwards. Installation Read chapter 3 ‘General Safety Instructions’...
BU-020 Operating Instructions for Temperature Controller ELT-GP1 Revision 4 20.12.2018 Settings and Operation All position numbers given here refer to Figure 1 in chapter. 2.2 ‘Controls And Displays’. Setting the temperature set-point (Target Temperature) • With the help of a screwdriver, or similar, briefly tap the control key (Pos. 3). The controller is now in setup mode for the setting the set-point •...
20.12.2018 Optional Features Other housing designs Another housing model is available for ELT-GP1 for connection of heaters with two cold ends, which has the necessary Pg-cable glands. Digital temperature display (ELT-ONA) The three-digit temperature display is limited to a range of -51 to +870 °C .
BU-020 Operating Instructions for Temperature Controller ELT-GP1 Revision 4 20.12.2018 Factory Optional Features Depending on where it is to be used, we can supply the controller not only as a 2-position controller but also in the following configurations: Controller Configuration...
Page 12
Advantages: Applications: Individual use thanks to modular design Refineries Accurate temperature maintenance Chemical & petrochemical industries Customized configuration possible Food processing industry Pharmaceutical industry Plastics industry Wastewater treatment plants Type ELT-GP1 6.54 Measurement and Control...
Page 13
Type ELT-GP1 Technical Information Data Optional Extensions for ELT-GP1, -GP2 and -GP3 Nominal voltage 230 V, 50 Hz ELT-OAA Analogue output Power consumption Max. 5 VA for ELT-GP-1/2/3 Controller temp. range 0 up to 100 °C 0–20 mA / 0–10 V 0 up to 200 °C...