Switching The Appliance On/Off; Switching On The Central Heating; System Controls; Setting The Domestic Hot Water - Bosch Worchester GREENSTAR ZWB 7-27 HE combi Installation And Servicing Instructions

Wall mounted condensing boiler for central heating and mains fed domestic hot water
Table of Contents

Advertisement

Commissioning
B Unscrew the condensation trap (358) and pull out, fill
with approx. 1/4 l of water and refit. Refer to fig. 29.
B Adjust charge pressure of expansion vessel to static
head of the central heating system (see page 26).
B Open all system radiator valves.
B Turn on service valves (170), fill central heating sys-
tem to pressure of 1 - 2 bar through the WRc
approved filling loop. Refer to fig. 29.
B Vent radiators.
B Refill heating system and set the pressure to 1 bar.
B Turn on cold water service cock (173). Refer to
fig. 29.
B Check that the gas type specified on the identifica-
tion plate matches that of the gas supply.
B Turn on gas cock (172). Refer to fig. 29.
5.2

Switching the appliance on/off

Switching on
B Switch on the appliance at the master switch (I).
The indicator lamp shows green and the display will
show the central heating flow temperature, when the
appliance is operating in the central heating mode.
6 720 610 333-04.1O
Fig. 30
If the display alternates between -II- and
i
the central heating flow temperature, the
trap filling programme is active.
The trap filling programme ensures that the condensa-
tion trap is filled after the appliance has been installed
or after the appliance has been out of use for a long
period or the mains supply has been interrupted. For
that reason, the appliance remains at minimum heating
output for 15 minutes.
Switching off the appliance
B Set the master switch to (0).
The green indicator lamp goes out.
B Always disconnect the appliance from
the power supply (fuse, circuit breaker)
before carrying out any work on the
electrical systems or components.
24
5.3

Switching on the central heating

The central heating flow temperature is adjustable
between 35°C and 88°C. Refer to table 12, page 26.
B Turn the temperature control
perature to a level appropriate to the type of central
heating system:
– Underfloor heating: e.g. setting "3"
(approx. 50°C)
– Low-temperature heating: setting "E"
(approx. 75°C)
– Central heating systems for flow temperatures up
to 88 °C: limited "max" setting for low-temperature
operation (see page 26).
When the burner is alight, the red indicator lamp
lights up.
Fig. 31
5.4

System controls

B Set room thermostat to the desired room tempera-
ture.
B Set outside - temperature driven control unit, if fitted.
Refer to the instructions with the control.
B Set the thermostatic radiator valves to the desired
settings.
5.5

Setting the domestic hot water

temperature and flow rate

5.5.1

Domestic hot water temperature

The hot water temperature can be set to between
approx. 40 °C and 60 °C.
This temperature is not shown on the display.
6 720 610 333-07.1O
Fig. 32
to set the flow tem-
6 720 610 333-05.1O
6 720 610 576 GB (02.05)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents