Powers HYDROGUARD XP LFMM430 Series Technical Instructions

Master tempering valves

Advertisement

Quick Links

Distributed By: M&M Control Service, Inc.
Technical Instructions
WARNING
!
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use infor-
mation can result in death, serious personal injury,
property damage, or damage to the equipment.
Keep this Manual for future reference.
!
WARNING
FAILURE TO COMPLY WITH PROPER INSTALLATION AND
MAINTENANCE INSTRUCTIONS COULD CONTRIBUTE TO THE
VALVE FAILURE.
This Hot Water Master Tempering Valves cannot be used for
tempering water temperature at fixtures. Severe bodily injury
(i.e., scalding or chilling) and/or death may result depending
upon system water pressure changes and/or supply water
temperature changes. ASSE standard 1016, 1069 or 1070 listed
devices should be used at fixtures to prevent possible injury.
These Hot Water Tempering Valves are designed to be
installed at or near the boiler or water heater. They are not
designed to compensate for system pressure fluctuations and
should not be used where ASSE standard 1016, 1069 or 1070
devices are required. These valves should never be used to
provide "anti-scald" or "anti-chill" service.
The components of the system must be of materials with a
construction capable of withstanding the high limit output tem-
peratures of the water heating source.
!
WARNING

Need for Periodic Inspection and Yearly Maintenance:

Periodic inspection and yearly maintenance by a licensed con-
tractor is required. Corrosive water conditions and/or unauthor-
ized adjustments or repair could render the valve ineffective for
service intended. Regular checking and cleaning of the valve's
internal components and check stops helps assure maximum
life and proper product function. Frequency of cleaning and
inspection depends upon local water conditions.
WARNING
!
You are required to consult the local building and plumbing
codes prior to installation. If the information in this manual is
not consistent with local building or plumbing codes, the local
codes should be followed. Inquire with governing authorities for
additional local requirements.
WARNING
!
Flush all pipes thoroughly before installation. Installation and
field adjustment are the responsibility of the installer.
www.mmcontrol.com/powershome.php
HYDROGUARD
®

Description

The Hydroguard
mixing valve designed for use in hot water distribution systems, in
compliance with ASSE 1017.

Specifications

Maximum Operating Pressure ............. 125 psi (861 kPa)
Maximum Hot Water Temperature .......200°F (93°C)
Minimum Hot Water Supply Temp ....... 5°F (3°C) Above Set-Point*
Temp. Adjustment Ranges
** Standard:........................................ 90 - 160°F (32 - 71°C)
Low: ..................................................... 60 - 90°F (16 - 32 C)
Hot Water Inlet Temperature Range .....120 -180°F (49 - 82°C)
Cold Water Inlet Temperature Range ... 40 - 80°F (4 - 27°C)
Listing......................................................... ASSE 1017
Certified .................................................... CSA B125
* With Equal Pressure
NOTICE
**
Low limit cannot be less than the cold water temperature.
For best operation, hot water should be at least 5°F (3°C)
above desired set point.
800-876-0036
XP Master Tempering Valves
Series LFMM430
MM430_For_PS-Sheet_Test_1.pdf
Page 1
Advanced Thermal Activation
n
XP LFMM430 series is a temperature actuated
®
n
847-356-0566
IS-P-MM430
09/14/2007

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HYDROGUARD XP LFMM430 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Powers HYDROGUARD XP LFMM430 Series

  • Page 1 Distributed By: M&M Control Service, Inc. www.mmcontrol.com/powershome.php 800-876-0036 847-356-0566 IS-P-MM430 HYDROGUARD XP Master Tempering Valves ® Series LFMM430 Technical Instructions WARNING Read this Manual BEFORE using this equipment. Failure to read and follow all safety and use infor- mation can result in death, serious personal injury, property damage, or damage to the equipment.
  • Page 2 5. When the Hydroguard supplies tempered water to self-closing ing practices. Flush all piping thoroughly before installation. and/or solenoid valves, provide a shock absorber (Powers Part Installation and field adjustment are the responsibility of the No. 460-353) on the discharge line.
  • Page 3 Distributed By: M&M Control Service, Inc. www.mmcontrol.com/powershome.php 800-876-0036 847-356-0566 Parts List - LFMM431, LFMM432, LFMM433, LFMM434 Index Description LFMM431 LFMM432 LFMM433 LFMM434 Checkstop Rebuild Kit LF390 800 LF390 800 LF390 801 LF390 801 Plunger Kit 390 802 390 802 390 803 390 803 Adjusting Screw 390 688...
  • Page 4 Seller’s equipment unless done by the Seller’s authorized personnel, or by written authority from the Seller. The Seller makes no guarantee with respect to material not manufactured by it. A Watts Water Technologies Company                         IS-P-MM430 1336 EDP# 6512300 © 2013 Powers...