Daikin FXNQ20MAVE Technical Data Manual

Daikin FXNQ20MAVE Technical Data Manual

Concealed floor standing unit
Hide thumbs Also See for FXNQ20MAVE:

Advertisement

technical data
Concealed Floor Standing Unit
FXNQ-MAVE

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FXNQ20MAVE and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Daikin FXNQ20MAVE

  • Page 1 technical data Concealed Floor Standing Unit FXNQ-MAVE...
  • Page 2: Table Of Contents

    • Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE TABLE OF CONTENTS FXNQ-MAVE Specifications ............2 Technical Specifications .
  • Page 3: Specifications

    U n i A V E e a l o o r Q - M I n d V R V F X N 1-1 Technical Specifications FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE Capacity Cooling 2.20 2.80 3.60...
  • Page 4: Electrical Specifications (60Hz)

    • Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE Specifications 1-2 Electrical Specifications (50Hz) FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE Current Minimum circuit amps (MCA) Maximum fuse amps (MFA) Full load amps (FLA) Voltage range Minimum -10% Maximum +10%...
  • Page 5: Safety Device Settings

    • Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE Safety device settings FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA PC BOARD FUSE 250V 10A “10 ƒC FAN MOTOR THERMAL PROTECTOR OFF: 135 / ON: 120 or less 3D034529C Options FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA...
  • Page 6: Control Systems

    • Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE Control systems Individual control systems FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA WIRED REMOTE CONTROL BRC1D52 INFRARED REMOTE CONTROL Heat pump BRC4C62 Cooling only BRC4C64 SIMPLIFIED REMOTE CONTROL BRC2A51 REMOTE CONTROL FOR HOTEL USE BRC3A61 Centralised control systems FXNQ20MA...
  • Page 7: Capacity Tables

    • Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE Capacity tables 5 - 1 Cooling capacity tables FXNQ-MA TC: Total capacity;kW - SHC: Sensible capacity;kW Indoor air temperature Outdoor Nominal 14.0WB 16.0WB 18.0WB 19.0WB 20.0WB 22.0WB 24.0WB Unit size air temp.
  • Page 8 • Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE Capacity tables 5 - 1 Cooling capacity tables FXNQ-MA TC: Total capacity;kW - SHC: Sensible capacity;kW Indoor air temperature Outdoor Nominal 14.0WB 16.0WB 18.0WB 19.0WB 20.0WB 22.0WB 24.0WB Unit size air temp.
  • Page 9: Heating Capacity Tables

    • Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE Capacity tables 5 - 2 Heating capacity tables FXNQ-MA Indoor air temperature ƒCDB Outdoor Unit Size Nominal capacity 16.0 18.0 20.0 21.0 22.0 24.0 air temperature ƒCDB ƒCWB -19.8 -20.0 -18.8 -19.0 -16.7...
  • Page 10 • Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE Capacity tables 5 - 2 Heating capacity tables FXNQ-MA Indoor air temperature ƒCDB Outdoor Unit Size Nominal capacity 16.0 18.0 20.0 21.0 22.0 24.0 air temperature ƒCDB ƒCWB -19.8 -20.0 -18.8 -19.0 -16.7...
  • Page 11: Dimensional Drawing & Centre Of Gravity

    • Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE Dimensional drawing & centre of gravity 6 - 1 Dimensional drawing FXNQ20,25MA 20 or more Top plate 2-12x18 slot hole Hole for fixing to the floor 150 or more Front face 1,000 or more Required installation space (Discharge flange)
  • Page 12 • Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE Dimensional drawing & centre of gravity 6 - 1 Dimensional drawing FXNQ50,63MA 20 or more Top plate 2-12x18 slot hole Hole for fixing to the floor 150 or more Front face 1,000 or more Required installation space (Discharge flange)
  • Page 13: Centre Of Gravity

    • Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE Dimensional drawing & centre of gravity 6 - 2 Centre of gravity FXNQ-MA Model FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA 4D034533B • VRV Systems • Indoor Units...
  • Page 14: Piping Diagram

    • Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE Piping diagram FXNQ-MA Gas pipe connection port Heat exchanger Liquid pipe connection port Filter Filter Electronic expansion valve 4D034245A • VRV Systems • Indoor Units...
  • Page 15: Wiring Diagram

    • Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE Wiring diagram 8 - 1 Wiring diagram FXNQ-MA Power supply 220-240V 220V 50Hz 60Hz Note 2 Input from outside Note 1 Transmission wiring central remote control Wired remote control Control box (Optional accessory) Indoor unit R2T •...
  • Page 16: Sound Data

    • Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE Sound data 9 - 1 Sound pressure spectrum FXNQ20,25MA 4D034534A FXNQ32MA 4D034535A Approximate Approximate threshold hearing for threshold hearing for continuous noise continuous noise Octave band center frequency (Hz) Octave band center frequency (Hz) NOTES NOTES Over all (dB):...
  • Page 17 • Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE Sound data 9 - 1 Sound pressure spectrum FXNQ63MA 4D034538A Approximate threshold hearing for continuous noise Octave band center frequency (Hz) NOTES Over all (dB): Scale 220V 240V (B, G, N is already rectified) 39.5 41.5 Measuring place: Anechoic chamber...
  • Page 18: Installation

    • Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE Installation 10 - 1 Suspension bolt pitch position FXNQ-MA • Positioning of holes for fastening to the wall • How to open/close the front panel Model FXNQ20,25MA FXNQ32,40MA FXNQ50,63MA 1,010 Open the lid of control panel (both left and right).
  • Page 19: Service Space

    • Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE Installation 10 - 2 Service space FXNQ-MA Model FXNQ20,25MA 1,030 FXNQ32,40MA 1,170 FXNQ50,63MA 1,450 NOTE Leave sufficient clearance for air inlet and maintenance. 3P086154-1-4 • VRV Systems • Indoor Units...
  • Page 20 Specifications are subject to change without environment. This challenge demands the eco design prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or and development of a wide range of products and an indirect damage, in the broadest sense, arising from or related to the use energy management system, resulting in energy and/or interpretation of this publication.

Table of Contents