Beck 930...EX Series Operating Instruction

The adjustable differential pressure switches
Hide thumbs Also See for 930...EX Series:

Advertisement

Beck GmbH
Druckkontrolltechnik
Ferdinand-Steinbeis-Straße 4
71144 Steinenbronn
Operating Instructions
The adjustable
Differential Pressure Switches
Model 930...EX
Ident:
060925-BA-930-R9-2016_englisch_Druckversion.doc
Operating instructions – Pressure Switch - Model-930...EX
Rev.9
Page 1 of 18

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 930...EX Series and is the answer not in the manual?

Questions and answers

Bissy Babu
May 2, 2025

What is the control Drawing number of 930.80U

1 comments:
Mr. Anderson
May 16, 2025

The control drawing number for the Beck 930.80U EX Series is 060925-BA-930-R9-2016_englisch_Druckversion.doc.

This answer is automatically generated

Summary of Contents for Beck 930...EX Series

  • Page 1 Beck GmbH Druckkontrolltechnik Ferdinand-Steinbeis-Straße 4 71144 Steinenbronn Operating Instructions The adjustable Differential Pressure Switches Model 930...EX Ident: 060925-BA-930-R9-2016_englisch_Druckversion.doc Operating instructions – Pressure Switch - Model-930...EX Rev.9 Page 1 of 18...
  • Page 2: Table Of Contents

    Telefax +49 7157 52 87-83 Amtsgericht Böblingen HRB 6050 Kreissparkasse Esslingen-Nürtingen (BLZ 611 500 20) 57 011 970 sales@beck-sensors.com Managing Directors: Rainer Beck, E-Mail S.W.I.F.T. ESSLDE66 IBAN: DE33 6115 0020 0057 0119 70 http://www.beck-sensors.com Hans-Peter Funk, Dr. Ernst Thielicke Internet Commerzbank Stuttgart (BLZ 600 400 71) 876 179 300 S.W.I.F.T.
  • Page 3: General Instructions

    Beck GmbH General Instructions Druckkontrolltechnik Safety Instructions Ferdinand-Steinbeis-Straße 4 71144 Steinenbronn 1 General Instructions These operating instructions contain all of the information that is required for an efficient start-up and safe operation of Model 930...EX pressure switches. Please read these operating instructions before carrying out installations, start-ups, maintenance and repairs.
  • Page 4: Safety Instructions For Potentially Explosive Areas

    Beck GmbH General Instructions Druckkontrolltechnik Safety Instructions Ferdinand-Steinbeis-Straße 4 71144 Steinenbronn 1.1.2 Safety instructions for potentially explosive areas The 930..EX pressure switch is suitable for use in areas where there is a risk of gas or dust explosion Please follow the applicable...
  • Page 5: Correct Purpose Of Use

    Beck GmbH Correct Purpose of Use Druckkontrolltechnik Application area Ferdinand-Steinbeis-Straße 4 71144 Steinenbronn 2 Correct Purpose of Use 2.1 Application area Purpose of use The adjustable differential pressure switches have the following main purpose Monitoring air flow in ventilation shafts for adequate Dilution of gasses that are hazardous to health or potentially explosive Air supply (fresh air) and/or exhaust air –...
  • Page 6: Storage And Transportation

    Beck GmbH Storage and Transportation Druckkontrolltechnik Packaging Ferdinand-Steinbeis-Straße 4 71144 Steinenbronn 3 Storage and Transportation 3.1 Packaging The equipment is protected by packaging. The packaging is environmentally compatible and recy- clable. The following main materials are used: Cardboard PE foam or PE film Please use appropriate recycling companies to dispose of the packaging 3.2 Storage and Transportation Conditions...
  • Page 7: Installation

    Beck GmbH Installation Druckkontrolltechnik Installation Ferdinand-Steinbeis-Straße 4 71144 Steinenbronn The following standards and directives are useful: EN 1127-1: Explosion protection – basic concepts and methodology Standards for areas with risk of gas or dust explosion (“G”, “D”): EN 60079-10: Classification of potentially explosive areas...
  • Page 8: 71144 Steinenbronn

    Beck GmbH Installation Druckkontrolltechnik Connection Ferdinand-Steinbeis-Straße 4 71144 Steinenbronn Power supply Each intrinsically safe operating material must have an associated operating material inserted before it, outside of the potentially explosive zone: Pay attention to maximum characteristics (U, I, P, L, C): Compare the information on the specification plate of the appropriate equipment and the pressure switch 930..EX...
  • Page 9: Start-Up

    Beck GmbH Start-up Druckkontrolltechnik Parameterisation Ferdinand-Steinbeis-Straße 4 71144 Steinenbronn Documentation Operating instructions, conformity declaration, EC design test certificate System and zonal plan Proof of adherence to explosion protection regulations (see Appendix 9.34) Equipment selection: category, Equipment Protection Level EPL, temperature class, explosion group, …...
  • Page 10: Maintenance / Service

    Beck GmbH Maintenance / Service Druckkontrolltechnik Time intervals Ferdinand-Steinbeis-Straße 4 71144 Steinenbronn 6 Maintenance / Service The equipment can only be guaranteed to operate safely and reliably in the long term if regular inspections and servicing are carried out. These include the following: For cleaning the devices it is necessary to take care that no electrostatic charging will be done (no high volume flow, cleaning only with damp cloth,…)
  • Page 11: Repairs

    Beck GmbH Repairs Druckkontrolltechnik Troubleshooting Ferdinand-Steinbeis-Straße 4 71144 Steinenbronn 7 Repairs The following points must be noted before carrying out any work whatsoever on the equipment: When work is being performed such as installation, making electrical connections or opening the housing, it must be ensured that...
  • Page 12: Disposal

    Beck GmbH Dismantling Druckkontrolltechnik Disposal Ferdinand-Steinbeis-Straße 4 71144 Steinenbronn ” must be followed Repairs Exposed cable (ends) must be marked, and it must be ensured that No electrical voltage is present Unintentional activation is not possible 8.1 Disposal The equipment is made from recyclable materials and is designed to make the housing and the electronics easy to separate.
  • Page 13: Appendix

    Beck GmbH Appendix Druckkontrolltechnik Technical data and dimensioned drawing Ferdinand-Steinbeis-Straße 4 71144 Steinenbronn 9 Appendix 9.1 Technical data and dimensioned drawing Temperature ranges Ambient temperature: from -20 °C to +85 °C Medium temperature: up to +85 °C Storage temperature: from -40 °C to +85 °C Diaphragm material Silicone;...
  • Page 14 Beck GmbH Appendix Druckkontrolltechnik Technical data and dimensioned drawing Ferdinand-Steinbeis-Straße 4 71144 Steinenbronn Types / Pressure ranges Type Adjustment range Switching Tolerance for trip pressure differential band of 930.80 EX 300 Pa 10 Pa ±15 % 500 Pa 20 Pa ±15 %...
  • Page 15: Dimensioned Drawings And Accessories

    Beck GmbH Appendix Druckkontrolltechnik Dimensioned drawings and accessories Ferdinand-Steinbeis-Straße 4 71144 Steinenbronn 9.2 Dimensioned drawings and accessories Operating instructions – Pressure Switch - Model-930...EX Rev.9 Page 15 of 18...
  • Page 16: Declaration Of Conformity

    Beck GmbH Appendix Druckkontrolltechnik Declaration of Conformity Ferdinand-Steinbeis-Straße 4 71144 Steinenbronn 9.3 Declaration of Conformity Operating instructions – Pressure Switch - Model-930...EX Rev.9 Page 16 of 18...
  • Page 17: Ec Design Test Certification

    Beck GmbH Appendix Druckkontrolltechnik EC design test certification Ferdinand-Steinbeis-Straße 4 71144 Steinenbronn 9.4 EC design test certification Note: More documentation for EC design test certification you can download from our website. Operating instructions – Pressure Switch - Model-930...EX Rev.9 Page 17 of 18...
  • Page 18: Proof Of Compliance With Explosion Protection Regulations

    Beck GmbH Appendix Druckkontrolltechnik Proof of compliance with explosion protection regulations Ferdinand-Steinbeis-Straße 4 71144 Steinenbronn 9.5 Proof of compliance with explosion protection regulations Project Name Date Requirement Complies with Requirement Complies with Application area Temperature Temperature Temp. (Gas) (Dust) (Gas)