ADDR.
WORD
PARAMETER
6455
1
IN AVG - Average (demand) neutral current : Alarm output
0 : Disable (*)
1 : Display only

2 : Display + discrete output 1

3 : Display + discrete output 2
4 : Display + discrete output 3
5 : Display + discrete output 4
6456
1
IN AVG - Average (demand) neutral current : Hysteresis (deadband)
0 to 999 : Specified value × 0.1 (%)
Factory setting : 0
6457
1
IN AVG - Average (demand) neutral current : ON delay time
0 to 999 : Seconds
Factory setting : 0
6459
2
P AVG - Average (demand) active power : High setpoint
Factory setting : 0
6461
2
P AVG - Average (demand) active power : Low setpoint
Factory setting : 0
6463
1
P AVG - Average (demand) active power : Alarm output
0 : Disable (*)
1 : Display only
2 : Display + discrete output 1
3 : Display + discrete output 2
4 : Display + discrete output 3
5 : Display + discrete output 4
6464
1
P AVG - Average (demand) active power : Hysteresis (deadband)
0 to 999 : Specified value × 0.1 (%)
Factory setting : 0
6465
1
P AVG - Average (demand) active power : ON delay time
0 to 999 : Seconds
Factory setting : 0
6467
2
Q AVG - Average (demand) reactive power : High setpoint
Factory setting : 0
6469
2
Q AVG - Average (demand) reactive power : Low setpoint
Factory setting : 0
6471
1
Q AVG - Average (demand) reactive power : Alarm output
0 : Disable (*)
1 : Display only
2 : Display + discrete output 1
3 : Display + discrete output 2
4 : Display + discrete output 3
5 : Display + discrete output 4
6472
1
Q AVG - Average (demand) reactive power : Hysteresis (deadband)
0 to 999 : Specified value × 0.1 (%)
Factory setting : 0
6473
1
Q AVG - Average (demand) reactive power : ON delay time
0 to 999 : Seconds
Factory setting : 0
6475
2
S AVG - Average (demand) apparent power : High setpoint
Factory setting : 0
6477
2
S AVG - Average (demand) apparent power : Low setpoint
Factory setting : 0
6479
1
S AVG - Average (demand) apparent power : Alarm output
0 : Disable (*)
1 : Display only
2 : Display + discrete output 1
3 : Display + discrete output 2
4 : Display + discrete output 3
5 : Display + discrete output 4
6480
1
S AVG - Average (demand) apparent power : Hysteresis (deadband)
0 to 999 : Specified value × 0.1 (%)
Factory setting : 0
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
53U
UNIT
%/10
Seconds
W
W
%/10
Seconds
var
var
%/10
Seconds
VA
VA
%/10
EM-6485-B Rev.21 P. 20 / 52