ADDR.
WORD
PARAMETER
6425
1
S - Apparent power : ON delay time
0 to 999 : Seconds
Factory setting : 0
6427
2
PF - Power factor : High setpoint
Factory setting : 0
6429
2
PF - Power factor : Low setpoint
Factory setting : 0
6431
1
PF - Power factor : Alarm output
0 : Disable (*)
1 : Display only
2 : Display + discrete output 1
3 : Display + discrete output 2
4 : Display + discrete output 3
5 : Display + discrete output 4
6432
1
PF - Power factor : Hysteresis (deadband)
0 to 999 : Specified value × 0.1 (%)
Factory setting : 0
6433
1
PF - Power factor : ON delay time
0 to 999 : Seconds
Factory setting : 0
6435
2
F - Frequency : High setpoint
Factory setting : 6500
6437
2
F - Frequency : Low setpoint
Factory setting : 4500
6439
1
F - Frequency : Alarm output
0 : Disable (*)
1 : Display only
2 : Display + discrete output 1
3 : Display + discrete output 2
4 : Display + discrete output 3
5 : Display + discrete output 4
6440
1
F - Frequency : Hysteresis (deadband)
0 to 999 : Specified value × 0.1 (%)
Factory setting : 0
6441
1
F - Frequency : ON delay time
0 to 999 : Seconds
Factory setting : 0
6443
2
I1 AVG thr. I3 AVG - Average (demand) current : High setpoint
Factory setting : 0
6445
2
I1 AVG thr. I3 AVG - Average (demand) current : Low setpoint
Factory setting : 0
6447
1
I1 AVG thr. I3 AVG - Average (demand) current : Alarm output
0 : Disable (*)
1 : Display only
2 : Display + discrete output 1
3 : Display + discrete output 2
4 : Display + discrete output 3
5 : Display + discrete output 4
6448
1
I1 AVG thr. I3 AVG - Average (demand) current : Hysteresis (deadband)
0 to 999 : Specified value × 0.1 (%)
Factory setting : 0
6449
1
I1 AVG thr. I3 AVG - Average (demand) current : ON delay time
0 to 999 : Seconds
Factory setting : 0
6451
2
IN AVG - Average (demand) neutral current : High setpoint
Factory setting : 0
6453
2
IN AVG - Average (demand) neutral current : Low setpoint
Factory setting : 0
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
53U
UNIT
Seconds
1/10 000
1/10 000
%/10
Seconds
Hz/100
Hz/100
%/10
Seconds
mA
mA
%/10
Seconds
mA
mA
EM-6485-B Rev.21 P. 19 / 52