8-2. FAN and FAN MOTOR
OPERATING PROCEDURE
1. Remove the control box cover according to the procedure
in section 8-1. CONTROL BOX.
2. Removing the fan motor cable
(1) Disconnect the connector (CNMF1) from the control board.
(2) Remove the cable through the rubber bush.
3. Removing the bottom plate
(1) Remove the fifteen fixing screws on the bottom plate to
remove it.
4. Removing the fan case
(1) Remove the eight fixing screws on the fan case to remove
it.
5. Removing the fan and fan motor
(1) Remove the two fixing screws and attachment on the fan
motor.
(2) Pull out the fan motor in the direction of the arrow.
23
Be careful on removing heavy parts.
FIGURES
Fig.1

Fig.2

Fig.3

Exercise caution when removing heavy parts.
Connector CNMF1