Project planning information
6 .5 Air connection
6 .5 .1 Indirect heating
Approx. 60 to 80 mbar air pressure should be present at
the air connection of the ECOMAX burner. Furthermore, the
pressure losses due to pipework and valves are to be taken
into consideration.
A quick opening, quick closing air valve or solenoid actuator
should be used.
Burner
Ecomax 0
Ecomax 1
Ecomax 2
Ecomax 3
Ecomax 4
Ecomax 5
ECOMAX · Edition 02.11
Butterfly valve/so-
Air valve
lenoid actuator
VR 20..N
–
VR 25..N
–
VR 40..N
–
VR 50..N
–
VR 65..N
–
–
BVHM 65/MB 7
ECOMAX 0
...
ECOMAX 4
Other types of control on request.