About This Document; Product Description; General; Product Specifications - Honeywell AA919 Installation And Technical Manual

Summing in-line amplifier
Table of Contents

Advertisement

Installation and Technical Manual for the
Summing In-Line Amplifier, Order Code AA919

About this Document

This document provides details for using the User Interface
Software that comes with the Summing In-Line Amplifier.
User Interface software can be used to:
Communicate with the Device
Configuring/Output Scaling of the Sensor's
Preload Tare
Shunt Calibration

1 | PRODUCT DESCRIPTION

1.1 | General

Honeywell's Summing In-Line Amplifiers are housed in a small
plastic package, which is connected between the transducer
and a readout instrument/UI running on a computer or laptop.
The Summing In-Line Amplifier supplies a regulated bridge
MOUNTING DIMENSIONS mm [in]
70,0
[2.8]
116,0
[4.6]
2 X Ø 7,0
3,0
[0.3]
[0.1]
SEE DETAIL A
26 GA TWISTED LEADS
2 X Ø 4,0
THRU
TEFLON INSULATED
[0.1]
0,91 m length – cable
[3 ft length – cable]
6,0
[0.2]
excitation voltage for the transducer and converts the millivolt
signal from the transducer to a 0-10 Vdc amplified signal. The
Summing In-Line Amplifier features include auto excitation
voltages, programmable gain settings, and a wide adjustment
range on the Span and offset value.

1.2 | Product Specifications

Power Requirements
Output Voltage
Accuracy
Operating Temperature Range
127,0
[5.0]
EARTH
(SHIELD)
21,0
[0.8]
008-0749-00
15 Vdc to 24 Vdc
0 Vdc to 10 Vdc
±0.25 % full scale span (FSS)
-10 °C to 60 °C [14 °F to 140 °F]
VCC
RED
OUTPUT
WHITE
GND
BLACK
GREEN
DETAIL A
Sensing and Internet of Things
ISSUE A
1

Advertisement

Table of Contents
loading