Indicates a situation that could result in minor or moderate 6.5.1 About connecting the electrical wiring......16 injury. 6.5.2 Precautions when connecting the electrical wiring ..16 6.5.3 Guidelines when connecting the electrical wiring ..17 Installer reference guide FTXTA30A2V1BW Split system air conditioner 4P518023-6E – 2019.04...
▪ In places where there is a risk of fire due to the leakage of comply with applicable legislation (on top of the flammable gases (example: thinner or gasoline), carbon fibre, instructions described in the Daikin documentation). ignitable dust. CAUTION ▪...
Page 4
1 General safety precautions WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed only by authorised persons. Installation space requirements NOTICE ▪ Pipework shall be protected from physical damage.
▪ The unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional charging of refrigerant. FTXTA30A2V1BW Installer reference guide Split system air conditioner 4P518023-6E – 2019.04...
WARNING is pulled loose from the stress relief. Make sure installation, servicing, maintenance, repair and applied materials follow the instructions from Daikin and, in addition, comply with applicable legislation and are performed by qualified persons only. In Europe and areas where IEC standards apply, EN/IEC 60335-2-40 is the applicable standard.
Technical engineering data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin extranet (authentication required). Installer reference guide at a glance 3.2.2...
Do NOT install the unit in places often used as work place. In case of construction works (e.g. grinding works) where a lot of dust is ▪ Daikin Industries Czech Republic s.r.o. declares that created, the unit MUST be covered.
Ø Ø ▪ Spacing. Install the unit at least 1.8 m from the floor and keep the following requirements in mind for distances from the walls and the ceiling: FTXTA30A2V1BW Installer reference guide Split system air conditioner 4P518023-6E – 2019.04...
Overview: Installation This chapter describes what you have to do and know on-site to install the system. Backside of the front panel Fixing tab Support 2 Close the front panel. Installer reference guide FTXTA30A2V1BW Split system air conditioner 4P518023-6E – 2019.04...
8 Pull the front grille up using the flat screwdriver and push towards the mounting plate. 6.2.4 To open the service cover 1 Remove 1 screw from the service cover. FTXTA30A2V1BW Installer reference guide Split system air conditioner 4P518023-6E – 2019.04...
4 Remove the electrical wiring box cover from the 2 rear hooks. INFORMATION The removed pipe port cover can be kept in the mounting Screw plate pocket. Electrical wiring box Rear hook Installer reference guide FTXTA30A2V1BW Split system air conditioner 4P518023-6E – 2019.04...
▪ Connecting the drain piping to the indoor unit To connect the piping on right-side, right-bottom, left-side or left- ▪ Checking for water leaks bottom, the pipe port cover MUST be removed. FTXTA30A2V1BW Installer reference guide Split system air conditioner 4P518023-6E – 2019.04...
Page 14
To connect the piping on right side, right-back, or right-bottom INFORMATION The factory default is right-side piping. For left-side piping, remove the piping from the right side and install it on the left side. Installer reference guide FTXTA30A2V1BW Split system air conditioner 4P518023-6E – 2019.04...
▪ NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material may dissolve and damage the system. Torque wrench Spanner Piping union Flare nut FTXTA30A2V1BW Installer reference guide Split system air conditioner 4P518023-6E – 2019.04...
▪ Insulation. Insulate the refrigerant piping, interconnection cable etc. from the terminal block. This could result in and drain hose on the indoor unit as follows: electrical shock or fire. Installer reference guide FTXTA30A2V1BW Split system air conditioner 4P518023-6E – 2019.04...
9 Pull the wires to make sure that they are securely attached, then retain the wires with the wire retainer. 10 Shape the wires so that the service cover fits securely, then close the service cover. FTXTA30A2V1BW Installer reference guide Split system air conditioner 4P518023-6E – 2019.04...
In case 2 indoor units are installed in 1 room, different addresses for 2 user interfaces can be set. 1 Remove the cover and the batteries from the user interface. 2 Cut the address jumper J4. Installer reference guide FTXTA30A2V1BW Split system air conditioner 4P518023-6E – 2019.04...
In cooling mode: 26~28°C, in heating mode: 20~24°C. Checking the "Checklist before commissioning". 3 The system stops operating 3 minutes after the unit is turned Performing a test run for the system. OFF. FTXTA30A2V1BW Installer reference guide Split system air conditioner 4P518023-6E – 2019.04...
Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required).
Page 21
Selector switch the accompanying documentation. SHEET METAL Terminal strip fixed plate Field supply Transformer Equipment NOT made by Daikin that can be combined with TC, TRC Transmitter product according instructions accompanying documentation.