Honeywell 7800 Series Installation Instructions Manual page 9

Relay modules
Hide thumbs Also See for 7800 Series:
Table of Contents

Advertisement

Test
Test
No.
Jumpers Voltmeter
4
None
6-L2
5
4-3
None
6
4-5
7-L2
7
4-8
None
8
4-9
None
9
4-10
None
10
4-17
None
11
12-13
18-L2
12
12-13
19-L2
13
13-14
19-L2
14
13-14
18-L2
15
13-15
None
Final
CAUTION
Electrical Hazard.
Can cause equipment damage.
After completing these tests, open the Master Switch and remove all test jumpers from the subbase terminals.
Also remove bypass jumpers from the low fuel pressure limits if used.
Table 3. Static Checkout. (Continued)
Normal Operation
Push and hold Stop Switch.
No voltage present at
terminal 6.
Alarm (if used) turns on.
Close burner control.
Recirculating/exhaust
blower fan starts, then line
voltage is present at
terminal 6.
1. Combustion air fan starts.
2. Line voltage at terminal 7
within 10 seconds.
Automatic pilot valve opens.
First stage valve
(DSI application only).
Ignition spark (if ignition
transformer connected).
Automatic main fuel valves
open. (DSI checks optional
second state fuel valve.)
Ignition spark (if ignition
transformer connected to
terminal 10.
Line voltage at terminal 17. 1. Listen for click or feel valve head for actuation of main
Firing rate motor drives
open; zero volts at terminal
18 after motor leaves Low
Fire position.
Firing rate motor reaches
High Purge Rate position;
120 Vac at terminal 19
when High Purge Rate
Switch closes.
Firing rate motor leaves
High Purge Rate Position;
zero Vac at terminal 19
when High Purge Rate
Switch opens.
Firing rate motor drives to
Low Purge Rate position;
120 Vac at terminal 18
when switch closes.
Adjust firing rate control
and watch tracking action of
the firing rate motor.
9
RM7838B, RM7838C 7800 SERIES RELAY MODULES
If Operation is Abnormal, Check These Items
Stop Switch.
1. Alarm.
2. Alarm Silencing Switch.
1. Combustion air fan circuit:
a. Manual switch on air fan motor.
b. Air fan power supply, overload protection, and starter.
2. Combustion Blower Air Flow Switch.
3. Alarm Silencing Switch.
4. Recirculating Air Flow Switch.
1. Listen for click or feel head of valve for activation.
2. Watch for spark or listen for buzz:
a. Ignition electrodes are clean.
b. Ignition transformer is okay.
Listen for and observe operation of the main fuel valve(s)
and actuator(s).
1. Watch for spark or listen for buzz:
a. Ignition electrodes are clean.
b. Ignition transformer is okay.
valve # 2.
1. Low Fire Start Switch.
2. Firing rate motor and transformer.
1. High Purge Rate Switch.
2. Firing rate motor and transformer.
1. High Purge Rate Switch.
2. Firing rate motor and transformer.
1. Low Purge Rate Switch.
2. Firing rate motor and transformer.
1. Firing rate control.
2. Firing rate motor and transformer.
32-00211—01