HPE-BNP1BUS –
FW4.01, from Feb. 2012
250 point integration of P1 FLN conforming devices in to BACnet MS/TP networks. Up to 32 P1 devices
may be connected to the gateway for read/write access of up to 250 data-points
Typical Applications
BACnet MS/TP network integration of P1 devices:
System 600, APOGEE Insight
TEC, ATEC, SCU, DPU, DLM
MEC Point Expansion units
HRW HP...P1 devices
Feature Summary
FIND function for initial network device/application identification
Diagnostic function for comms verification and trouble-shooting
Continuous poll for point status changes
User set period for complete point status update
Scaling table for known and customised sensor types
HRW Limited
P1 FLN Gateway to BACnet MS/TP
504-505, 5/F, Wai Wah Commercial Centre
6 Wilmer Street, Sai Ying Pun
Hong Kong
Ph +852 2546 7402
Fax +852 2546 7403
www.hrw.hk

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HPE-BNP1BUS and is the answer not in the manual?

Questions and answers

Summary of Contents for HRW HPE-BNP1BUS

  • Page 1 HPE-BNP1BUS – P1 FLN Gateway to BACnet MS/TP FW4.01, from Feb. 2012 250 point integration of P1 FLN conforming devices in to BACnet MS/TP networks. Up to 32 P1 devices may be connected to the gateway for read/write access of up to 250 data-points...
  • Page 2: Table Of Contents

    INSTALLATION & COMMISSIONING ......................15 CONNECTIONS ..............................16 DIMENSIONS ................................16 TECHNICAL DATA .............................17 ORDERING INFORMATION ..........................17 HPE-BNP1BUS..............................17 ...............................17 CCESSORIES HP_BN S ..........................17 THER ERIES EVICES HRW HPE-BNP1BUS V401 Manual 120201.doc E. & O. E. / Subject to change without notice Page 2 of 18...
  • Page 3: Operation Overview

    (such as the BMS)  For normal reading of the P1 network points should always be at NULL priority HRW HPE-BNP1BUS V401 Manual 120201.doc E. & O. E. / Subject to change without notice Page 3 of 18...
  • Page 4: Terminal Mode

    For successful communication between HyperTerminal and the device, initial Properties setup of HyperTerminal should be as per the screen prints below. ‘Connect to’ Comm Configuration: ‘Settings’ General: 9600 ‘Settings’ ASCII Setup: HRW HPE-BNP1BUS V401 Manual 120201.doc E. & O. E. / Subject to change without notice Page 4 of 18...
  • Page 5: Additional Settings

    (TTTTTTT…). After five (5) T’s have been sent to the device it will switch to terminal mode. At this point the BACnet activity on the network will be halted and the device will display the default user screen. HRW HPE-BNP1BUS V401 Manual 120201.doc E. & O. E. / Subject to change without notice...
  • Page 6: Bacnet Configration Commands

    Auto X after 240sec without key entry. After Exit HyperTerminal no longer eXit unplug the HPECOM cable to allow communication active network communication to take place HRW HPE-BNP1BUS V401 Manual 120201.doc E. & O. E. / Subject to change without notice Page 6 of 18...
  • Page 7: P1 Configuration Commands

    Auto X after 240sec without key entry. After Exit HyperTerminal no longer eXit unplug the HPECOM cable to allow communication active network communication to take place HRW HPE-BNP1BUS V401 Manual 120201.doc E. & O. E. / Subject to change without notice Page 7 of 18...
  • Page 8: P1 Integration

    Each devices’ active Application # is also identified and displayed. Below we see P1 address 2 has responded and it’s application is #162. Consequently it is temporarily displayed under the HPE-BNP1BUS point 4 listing, including the application number.
  • Page 9: Sensor Type (Scaling) Table

    Shift decimal place left two places = -2 therefore enter 12=-2 2) Intercept of -48 a. Input Base = Intercept / Slope = -48/.25 = -192 therefore enter 11=-192 HRW HPE-BNP1BUS V401 Manual 120201.doc E. & O. E. / Subject to change without notice Page 9 of 18...
  • Page 10: Standard Sensor Types

    Standard Sensor Types A number of standard Sensor Types are preconfigured reflecting known TEC and HRW device input/output parameters. P1 Sensor types Programming Value Description Type 0 - HRW HPE/HPC = -10…92°C * (0.1/-10) Type 1 - TEC Slope 0.14 / intercept -8.889 Slope 0.28 / intercept -3.056...
  • Page 11 The value in ( ) is the time pending reinstated after a power failure until next scan HRW HPE-BNP1BUS V401 Manual 120201.doc E. & O. E. / Subject to change without notice Page 11 of 18...
  • Page 12: Data Base Mapping Tool

    Although all configuration can be typed directly in to the gateway via the terminal program, by email request or by download from www.hrw.hk, Resources/Tools, you may use our mapping Tool for creation of a table of data base settings which can be downloaded to the gateway as a text file (*.txt).
  • Page 13: Scaling Table Configuration

    The reference Slope and Intercept values are taken from the P1 device documentation. Entering these two values automatically calculates the ‘Base’ value required by the HPE-BNP1BUS. The ‘10’s Multiplier’ and ‘1’s Multiplier’ values must be manually entered in reference to the P1 device’s documented slope value.
  • Page 14: Download Text File

    Enter to force a scan, then stop the capture. Open the resultant text file with Word to view a formatted record of the communication for analysis. HRW HPE-BNP1BUS V401 Manual 120201.doc E. & O. E. / Subject to change without notice...
  • Page 15: Installation & Commissioning

    24Vac power supplies cannot be guaranteed, we recommend that a repeater be used to provide isolation of the sections of the network having differing earth potential HRW HPE-BNP1BUS V401 Manual 120201.doc E. & O. E. / Subject to change without notice...
  • Page 16: Connections

    If using HDA0002 DIN rail adapter brackets the overall depth from the gear plate to the front surface of the device is 45.5mm HRW HPE-BNP1BUS V401 Manual 120201.doc E. & O. E. / Subject to change without notice Page 16 of 18...
  • Page 17: Technical Data

    VAV / Universal Controller, 13 Point, BACnet MS/TP, 24Vac HPE-BNMBUS BACnet gateway for M-Bus devices (EN1434), 250 point, 24Vac HPE-BNMOD BACnet gateway for Modbus devices, 250 point, 24Vac HRW HPE-BNP1BUS V401 Manual 120201.doc E. & O. E. / Subject to change without notice Page 17 of 18...
  • Page 18 Notes: HRW HPE-BNP1BUS V401 Manual 120201.doc E. & O. E. / Subject to change without notice Page 18 of 18...