HPE-BNSMA – SMA Gateway to BACnet MS/TP FW4.01 250 point integration of SMA protocol devices in to BACnet MS/TP networks. Up to 32 SMA devices may be connected to the gateway for read access of up to 250 SMA data-points Typical Applications BACnet MS/TP network integration of SMA devices such as…...
INSTALLATION & COMMISSIONING ......................14 CONNECTIONS ..............................15 DIMENSIONS ................................15 TECHNICAL DATA .............................16 ORDERING INFORMATION ..........................16 HPE-BNSMA..............................16 ...............................16 CCESSORIES HP_BN S ..........................16 THER ERIES EVICES HRW HPE-BNSMA V401 Manual 111201.doc E. & O. E. / Subject to change without notice Page 2 of 16...
(such as the BMS) For normal reading of the SMA network points should always be at NULL priority HRW HPE-BNSMA V401 Manual 111201.doc E. & O. E. / Subject to change without notice Page 3 of 16...
For successful communication between HyperTerminal and the device, initial Properties setup of HyperTerminal should be as per the screen prints below. ‘Connect to’ Comm Configuration: ‘Settings’ General: 9600 ‘Settings’ ASCII Setup: HRW HPE-BNSMA V401 Manual 111201.doc E. & O. E. / Subject to change without notice Page 4 of 16...
BACnet activity on the network will be halted and the device will display the default user screen, an example of which follows: HRW HPE-BNSMA V401 Manual 111201.doc E. & O. E. / Subject to change without notice Page 5 of 16...
Auto X after 240sec without key entry. After Exit HyperTerminal no longer eXit unplug the HPECOM cable to allow communication active network communication to take place HRW HPE-BNSMA V401 Manual 111201.doc E. & O. E. / Subject to change without notice Page 6 of 16...
Auto X after 240sec without key entry. After eXit Exit HyperTerminal no unplug the HPECOM cable to allow network communication longer active communication to take place HRW HPE-BNSMA V401 Manual 111201.doc E. & O. E. / Subject to change without notice Page 7 of 16...
For instance, to change device with serial number 6830 to network address 4 then enter: SNA6830=4 HRW HPE-BNSMA V401 Manual 111201.doc E. & O. E. / Subject to change without notice Page 8 of 16...
Activate the DIAG display to see these characters. On the BACnet side this data will be provided in numerical form and must be translated accordingly by the BACnet system. HRW HPE-BNSMA V401 Manual 111201.doc E. & O. E. / Subject to change without notice...
10) then using command SC enter as follows: SC6=1 The SC prefix indicates that only the Scaling portion of point 6 is being configured. HRW HPE-BNSMA V401 Manual 111201.doc E. & O. E. / Subject to change without notice Page 10 of 16...
Enter E to enable the SMA communication and enter W to write the enabled state so that it will still be enabled after a power failure. Note: To disable enter E again to toggle from enabled to disabled state. HRW HPE-BNSMA V401 Manual 111201.doc E. & O. E. / Subject to change without notice Page 11 of 16...
4 starting point. The AII type as illustrated above is 1 Word data whereas there may be 2 Word data or Float4 data within a particular channel list. HRW HPE-BNSMA V401 Manual 111201.doc E. & O. E. / Subject to change without notice...
0 after four bad reads. Entering DF=1 will revert to factory default (hold last valid read value). HRW HPE-BNSMA V401 Manual 111201.doc E. & O. E. / Subject to change without notice...
24Vac power supplies cannot be guaranteed, we recommend that a repeater be used to provide isolation of the sections of the network having differing earth potential HRW HPE-BNSMA V401 Manual 111201.doc E. & O. E. / Subject to change without notice...
If using HDA0002 DIN rail adapter brackets the overall depth from the gear plate to the front surface of the device is 45.5mm HRW HPE-BNSMA V401 Manual 111201.doc E. & O. E. / Subject to change without notice Page 15 of 16...