Download Print this page

Emerson HANCOCK Installation, Operation And Maintenance Instructions

Cast steel - gate, globe and check valves

Advertisement

Quick Links

HANCOCK CAST STEEL - GATE, GLOBE AND CHECK VALVES
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
Before installation these instructions must be fully read and understood
Instructions for DN 50 - 600 (NPS 2 - 24)
ASME class 150, 300 and 600 bolted bonnet
cast steel valves.
SAFETY NOTICE
It is essential that a safe system of work
should be adopted before any maintenance
work is done on a valve. The following safety
considerations should be taken in to account
when preparing maintenance instructions.
Before removing valves from a pipework
system or dismantling a valve to carry out
maintenance, it will be necessary to open,
or partially open, the valves and to flush the
system to remove all traces of dangerous
fluids and pressures.
It is important to recognize the danger
associated with the removal of the stem
packing gland with pressure in the pipework
system and the use of the backseat should not
be regarded as a device permitting repacking
of the stem packing gland whilst the valve
is under pressure as this is recognized as
dangerous practise.
1 GENERAL INSTALLATION INSTRUCTIONS
1.1 General
The installation procedure is a critical stage in
the life of a valve and care should be taken to
avoid damaging the valve.
Emerson.com/FinalControl
1.2 Inspection
Before carrying out a valve installation, it is
important to determine whether the valve is in
a satisfactory condition.
The following generally applicable procedure
may be helpful in avoiding subsequent valve
problems and should be observed.
a) Carefully unpack the valve and check tags,
identification plates, direction of rotation
of handwheels etc, against bill of material,
specifications, schematics etc.
b) Make a point of noting any special warning
tags or plates attached to or accompanying
the valve, and take any appropriate action.
c) Check the valve for any marking indicating
flow direction. If the flow direction is
indicated, appropriate care should be
exercised to install the valve for proper
flow direction.
d) As far as is practicable, inspect the valve
interior through the end ports to determine
whether it is reasonably clean, free from
foreign matter and harmful corrosion.
Remove any special packing materials,
such as blocks used to prevent disk
movement during transport and handling,
and anti-corrosion packs. Wipe clean from
preservation coatings, particularly seatings.
e) If practicable, cycle the valve through open
and close. Check guides or seat faces, etc.
f) Immediately prior to valve installation,
check the pipework to which the valve is
to be fastened for cleanliness and freedom
from foreign materials.
© 2017 Emerson. All Rights Reserved.
VCIOM-02504-EN 19/04

Advertisement

loading

Summary of Contents for Emerson HANCOCK

  • Page 1 HANCOCK CAST STEEL - GATE, GLOBE AND CHECK VALVES INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Before installation these instructions must be fully read and understood 1.2 Inspection Before carrying out a valve installation, it is important to determine whether the valve is in a satisfactory condition.
  • Page 2 HANCOCK CAST STEEL - GATE, GLOBE AND CHECK VALVES INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS 1.3 Flanged joint assembly Particular care is necessary when welding Pipe flanged joints depend on compressive valves into the line. Considerable distortion, deformation of gasket material between the resulting in line strains, may occur if valves facing flange surfaces for tight sealing.
  • Page 3: Gate Valves

    HANCOCK CAST STEEL - GATE, GLOBE AND CHECK VALVES INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS 2 GATE VALVES 2.2 Maintenance 2.1 Installation and operation Gland leakage 2.1.1 Prior to installation CAUTION Valves not required for immediate use should be stored under clean conditions to reduce the...
  • Page 4 HANCOCK CAST STEEL - GATE, GLOBE AND CHECK VALVES INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS 3 GLOBE VALVES Valves are supplied with this assembly fully lubricated and should operate smoothly. 3.1 Installation and operation To avoid problems from developing, the 3.1.1 Prior to installation...
  • Page 5: Swing Check Valves

    HANCOCK CAST STEEL - GATE, GLOBE AND CHECK VALVES INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS 4 SWING CHECK VALVES They may be fitted in horizontal or vertical (flow-upwards) pipelines, or any in-between 4.1 Installation of valve lines with flow-upward. They must always be 4.1.1 Prior to installation...
  • Page 6 Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user. Hancock is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson and the Emerson logo are trademarks and service marks of Emerson Electric Co.