HMI (Human-Machine Interface)
Push-button operation
Activity
Enter / leave addressing mode
Reset to factory settings
PL-Link connection test
1)
Function or part of the function available in PL-Link operation only
LED colors and patterns
Color
Off
Green
Orange
Red
1)
Function or part of the function available in PL-Link operation only
Addressing and bus test with push button
The rotary actuators can be set into addressing/programming mode by push-button:
Press push button (<1 s)
KNX bus wiring OK ⇓ LED turns red until addressing/programming is finished
KNX bus wiring not OK ⇓ LED stays dark
Reset with push button
The rotary actuators can be reset by push-button:
Press push button >20 s
LED flashes orange
Device restarts
All parameters are reset to the default values.
A6V10725318_en--_e
2018-06-05
Push-button operation
Press button <1 s
Press button >20 s
1)
Press key >2 s and <20 s
Pattern
Description
---
Fault free operation or device not powered
steady
Connection test successful
flashing
a) Factory reset in progress
b) When a connection test was triggered: wait
steady
a) Device is in programming/addressing mode
b) When a connection test was triggered: Connection test failed
Confirmation
LED turns red or gets off
LED flashes orange until device
restarts
LED flashes 1x orange
1)
1)