Dorma ES 200 Easy Quick Start Manual
Hide thumbs Also See for ES 200 Easy:

Advertisement

Quick Links

DORMA
1. Commissioning
1. Commissioning
1.1 Please note:
Work on electrical
equipment
by properly qualified electricians.
Power supply (by others) with 16 A fuse protection
must be available.
Power cord must be double-insulated,
NYM. Do not use flat webbed house wires!
The maximum cable length of the external
components must not exceed 30 m.
1.2 Basic requirements:
• The operator is fully assembled.
• The protective earth (PE) is connected.
• The safety sensors are connected.
• Components supplied separately, such as
program switches, activators, radar motion
detectors, Night-/Sank
EMERGENCY OFF pushbuttons are installed
and connected .
• The end stops are adjusted so that both active
panels touch the end stops when the panels
have reached maximum opening width.
• When the door is closed, the active and the
passive door panel must not collide with the
sealing profiles.
• The door has to run smoothly. Check the length
of the connection screws of the toothed belt
Ij\
and replace the screws if necessary.
Lll
Update (small motor)
The ES 200 control unit can be installed as a
replacement for older systems with GR 63x25 motors.
However, a special cable for the incremental encoder
with a pulse devider is required.
The following
procedure has to be observed:
- Install hardware.
- Set program switch to "OFF" and activate the
EMERGENCY OFF pushbutton.
- Reset system to original settings (factory settings):
Press and hold service key, switch on power supply.
- Release the service key as soon as the 8 on the
seven-segment display blinks twice.
- Adjust the GR 63x25 Motor via the pushbuttons on
the basic module (b
- Unatch the EMERGENCY OFF pushbutton.
- Perform a learning cycle.
A
Safeguarding of door:
The safety measures to safeguard the doors must
be made in accordance with the local (country-
specific) regulations.
Where sliding doors shall be operated in Germany
DIN 18650
according to
Standard), the specifications
industrial standard must be observed.
See: WN 057015 45-5-32
Easy
ES 200
ES 200
ES 200-20
ES 200 C048/
DAC 300
may only be performed
for example:
keyswitches and
=
0) or via PDA.
(German Industrial
stated in this
1.3 First Commissioning
1.3.1
Open the sliding panels half way.
ES200 Easy:
1.3.2
Set program switch to AUTOMATIC
ES200 I ES200-2D:
Set program switch to OFF
1.3.3
Unlatch the EMERGENCY OFF pushbutton
and bridge the light barriers. Duri ng the first
commissioning
of the system the infrared light
curtains or light barriers shall be replaced by
jumpers.(See connection diagram 056632-45532)
Following the iearning cycle, the first closing cycle
and the parameterization
of the control unit, the
infrared light curtains or light barriers have to be
connected and checked for proper functioning .
1.3.4
Insert the power plug and connect immediately
thereafter the rechargeable battery pack. (within max. 8 sec.)
.&
The door must perform a closing cycle at low
(creep) speed.
If the door performs an opening cycle, the
system must be set back to original sellings.
Disconnect the power plug so that the opening
cycle stops.
Proceed on 2. original sellings
If the door performs a closing cycle, proceed with the
learning cycle starting with the door closed.
Please note:
The light barriers and radar motion detectors are
disabled during the learning cycle, as it has to be
performed without
interruptions.
In case that a fauit or error should occur during this
procedure, the learning cycle will be interrupted
needs to be started anew.
1.3.5
Performing the learning cycle:
ES200Easy.
press and hold SELECT button for 3 sec. Then the
door will perform a learning cycle.
ES200/ES 200-2D/ES 200 C048I DAC300:
press SERVICE button.
• Press and hold SERVICE/SELECT bullon until
the door commences with the learning cycle. The
external segments of the 7-segment display will
illuminate
in turn.
• The door accelerates in order to determine the
door weight.
• The door opens at low (creep) speed to
determine the opening width.
~
DORMA
and

Advertisement

loading

Summary of Contents for Dorma ES 200 Easy

  • Page 1 Easy ES 200 ES 200 DORMA • ES 200-20 DORMA ES 200 C048/ DAC 300 1. Commissioning 1.3 First Commissioning 1. Commissioning 1.3.1 Open the sliding panels half way. 1.1 Please note: ES200 Easy: 1.3.2 Work on electrical equipment may only be performed by properly qualified electricians.
  • Page 2 Easy ES 200 ES 200 DORMA • DORMA ES 200-20 ES 200 C048 DAC 300 1. Commissioning Country-specific settings for first The parameters registered during the learning commissioning. cycle are now stored and an ES 200C048 8 flashes twice on the 7-segment display.
  • Page 3: Troubleshooting

    How does the control unit respond to a short circuit? ES 200 Easy/ES 2QO-2D/ES 200 C048/DAC 300 The 27 V power supply for radar motion detectors, the locking device etc. is short circuit proof. In the event of...
  • Page 4 ES 200 Easy DORMA • ES 200 ES 200 20 1il~ 6. Troubleshooting Door remains open in the program Detector is emitting a continuous Remove connector of radar motion switch settings: AUTOMATIC, signal detector. If fault is cured by this,...

This manual is also suitable for:

Es 200Dac 300Es 200-2dEs 200 co48