5.5.2 Integrator control function
Command
C:I_LIM
C:I_ACT
The integrator function is controlled by this command.
C:I_LIM
Limitation of the integrator range (faster control function by reduced pressure overshoots). By a
high nonlinearity of the valve the LIM value must be sufficient to compensate it.
C:I_ACT Controls the integrator function. To reduce pressure overshoots, an activation point for the integra-
tor can be programmed via the (I_ACT) value. The integrator is activated if the actual pressure is
higher than the programmed threshold.
Page 25 of 42
Parameter
X
x= 0... 10000
X
x= 0... 10000
MDR-133-*-2030
Unit
Group
0,01 %
STD
0,01 %
29.08.2019