Under-Voltage Protection - Sevcon MillipaK Manual

Pump controller
Table of Contents

Advertisement

Controller Protection
______________________________________________________________________________

Under-voltage protection

In order to prevent a sudden loss in power, the controller will begin to linearly ramp down the
current limit, once the average battery voltage falls below a pre-set under-voltage start level. The
current will be ramped down to 0 and a 7 flash fault indicated if the averaged battery voltage falls
below the under-voltage cut-out level.
Nominal Battery
Voltage
The following calibrator menu items are used to set these values.
Low Voltage Start
Calibrator Menu Reference:
Minimum
Maximum
Low V
System
Cutout
Voltage
Low Voltage Cutout
Calibrator Menu Reference:
Minimum
Maximum
14.5V
Low V Start 0.5V
MillipaK PUMP Controller Manual
Under-voltage
Cutout
24 V
36 V
48 V
Immediate
11.03
Step Size
Typical Value
0.5V
18.0V
Immediate
11.04
Step Size
Typical Value
16.0V
Page 38
Controller Protection/Under-voltage protection
Under-Voltage Start
(adjustable)
14.5V
Under Voltage Cut-
14.5V
out up to System V
14.5V
07/11/05