[2] (E)M350 to 500
(1) When routing the wiring through the front of the unit
Power cable size (mm
)
2
2, 3.5, 5.5
8, 14
21, 26, 33
84, 67, 53
Cable strap
Power cable
Transmission cable
The length of the section after the cable access hole must be at least 1100 mm (43 in).
<Notice>
・Do not remove the ground wire that connects Main Box and Inverter Box.
・Install the transmission cable as shown in the figure above so that the cable is long enough for the Main Box to be
moved for servicing.
・If there are any gaps around the power cable and transmission cable, please be sure to fill these in with a suitable
material to prevent snow from entering, which may cause damage to the electrical parts, and to protect your hands
from direct contact with cables.
・When putting the power cable through the knockout hole without using a conduit tube, deburr the hole and protect
the power cable with protective tape.
・Use a conduit tube to narrow down the opening if there is a possibility of small animals entering the unit.
・When taking the conduit tube out from the bottom part of the unit, caulk around the tube opening to prevent water
infiltration.
WT09050X01
Knockout hole to be used
Knockout hole 2
Knockout hole 4
Knockout hole 3
Knockout hole 5
(2) When routing the wiring through the bottom of the unit
Fill the gap.
49