PUMP CURRENT DRAW, WINDING RESISTANCE
MODEL
HP
VOLTAGE
WGL20-01
2
208
WGL20-21
2
230
WGL20-03
2
208
WGL20-23
2
230
WGL20-43
2
460
*WARNING: On 3 phase panels, overload heater elements are not factory installed in the overload relay. Elements must be purchased
separately and correspond with the above chart. This must be done before the panel is put into service. Failure to install the
elements before the panel is put into service, or failure to install the correct size elements, may result in pump failure. All pump
and panel warranties will be void if the above guidelines are not followed
All standard CGL (Simplex) Series control panels manufactured after
OVERLOAD HEATER SELECTION*
PHASE
RPM
F.L.A.
1
3450
15.0
1
3450
12.5
3
3450
9.5
3
3450
8.4
3
3450
4.2
NOTICE
July 1, 1993 will have the following changes:
Previous Part No.
Pump Run
21973A002 (Holder)
Light Ass'y.
21974A001 (Bulb)
Seal Leak
21973A001 (Holder)
Light Ass'y.
21974A001
RESISTANCE
L.R.A. BLK-WH BLK-RED WH-RED HEATER
52.5
1.14-1.26 4.63-5.11
44.0
1.46-1.62 7.20-8.00
34.0
2.65-2.93 2.65-2.93
32.5
3.12-3.45 3.12-3.45
16.3
12.5-13.8 12.5-13.8
New Part No.
21973A013
21973A012
(Bulb)
9
HEATER NO.
5.77-6.37
8.66-9.62
2.65-2.93
K50
13621A091
3.12-3.45
K49
13621A062
12.5-13.8
K34
13621A104
23833A150 11/08/12