Mean Well LCM-25KN Instruction Manual

Led driver with knx interface

Advertisement

Quick Links

LCM-25/40/60KN
LED Driver with KNX
Interface
Instruction Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LCM-25KN and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Mean Well LCM-25KN

  • Page 1 LCM-25/40/60KN LED Driver with KNX Interface Instruction Manual...
  • Page 2: Table Of Contents

    Content ....................... 1.Overview ....................1.1 Overview devices ................. 1.2 Usage & possible applications ................1.3 Displays and operating elements ....................1.4 Circuit diagrams ................1.5 Information at the ETS-Software ......................1.6 Starting up ..................2.Communication Objects ....................2.1 Summary and Usage ..................
  • Page 3: Overview

    The manual refers to the following devices: (Order Code respectively printed in bold type): LCM-25KN INPUT: 180 ~ 295VAC 47 ~ 63Hz, OUTPUT: 350mA ~ 1050mA, 6 ~ 54V LCM-40KN INPUT: 180 ~ 295VAC 47 ~ 63Hz, OUTPUT: 350mA ~ 1050mA, 2 ~ 100V LCM-60KN INPUT: 180 ~ 295VAC 47 ~ 63Hz, OUTPUT: 500mA ~ 1400mA, 2 ~ 90V 1.2 Usage &...
  • Page 4: Circuit Diagrams

    1.4 Circuit diagrams Configuration 1:General use KNX Bus ..Configuration 2:With push dimming Push Button KNX Bus ..KNX bus need to be connected when using PUSH Dimming. The detailed function of PUSH dimming, please refer to 3.5 Push dim port. The maximum length of the cable between the push button and driver is 20 meters.
  • Page 5 Configuration 3:With AC/DC input monitor KNX Bus ..KNX bus need to be connected when using AC/DC input monitor. The detailed function of AC/DC input monitor(emergency lighting), please refer to 3.5 Push dim port. Configuration 4:Synchronization operation LCM-40KN LCM-40 (Master) (Slave) KNX Bus ..
  • Page 6: Information At The Ets-Software

    1.5 Information at the ETS-Software Selection at the product database: Manufacturer: MEANWELL Enterprises Co.Ltd. Product family: Output. Product type: KLD Product name: addicted to the used type, e.g.: LCM-40KN, LED Driver with KNX interface Order number: addicted to the used type, e.g.: LCM-40KN 1.6 Starting up After wiring, the allocation of the physical address and the parameterization of every channel follow: (1)Connect the interface with the bus, e.g.
  • Page 7 This Communication Object is only shown after Switch activating in the parameter settings and can be 1 bit Automatic 2 Normal dimmer (DPT 1.001) used for calling of absolute brightness values with a 1 Bit command. This Communication Object is only shown after Switch activating in the parameter settings and can be Automatic 3...
  • Page 8: Reference Ets-Parameter

    This Communication Object is only shown when Operating hours Time lag(s) (set value, in Counting of operating hours & CLO is active and can be (DPT 13.100) seconds) used to overwrite the operating time the device counted Operating hours 4 Bytes This Communication Object is only shown when Operating hours Counter pulse...
  • Page 9: Time Functions

    3.3 Time function The dimming actuator has the opportunities of connecting different time functions. Besides the normal on/off delay, an additional staircase function with different sub functions is available. 3.3.1 On/ Off delay The on and off delay allows a delayed switching. The following chart shows this parameter: The chart shows the dynamic range for this parameter: Dynamic range ETS-text...
  • Page 10 The chart shows the dynamic range for this parameter: Dynamic range Comment ETS-text [default value] Duration of staircase light 1s -30,000s Duration of the switching process. [90s] active Prewarning Activates the prewarning. not active Prewarning 1-30,000 Is only shown, when the prewarning is activated. duration in [s] [10s] Value of dimming down...
  • Page 11: Push Dim Port

    Push dim port Push dimming or switch dimming is a dimming method using a simple retractive switch to realize dimming function. Normally a short press of the switch turns the driver on/off, while a long push dims the brightness of light, the dimming direction changes with each long press.
  • Page 12: Operating Hours & Constant Light Output (Clo)

    Dynamic range Comment ETS- text [default value ] START/STOP dimming process starts with a telegram START/STOP dimming Dimming mode BRIGHTER or DARKER to increase or decrease Dimming steps light intensity and ends with a STOP telegram Brightness change on every Parameterizes a desired dimming step 100%, 50%, 25%, 12%, 6%, 3%, 1% [3%]...
  • Page 13 3.6.1 Operating hours Operating hours can be used to monitor service time of the lumiaire and used to prepare a replacement before the lamp is over its lifetime so as to maintain a constant level of illumination for the building. The chart shows the dynamic range for this parameter: Dynamic range Comment...
  • Page 14: Absolute Values

    The chart shows the dynamic range for this parameter: Dynamic range Comment ETS- text [default value ] 1(x100hours) - 500(x100hours) 10% - 100% Parameterizes the first stage of CLO Scheduled division 1 [80%] [100(x100hours)] 1(x100hours) - 500(x100hours) Scheduled division 2 Parameterizes the 2nd stage of CLO 10% - 100% [150(x100hours)]...
  • Page 15: Specific Dimming Settings

    Via the parameter “Value of start up”, an absolute value for switching on can be assigned to the channel. The value for startup contains the whole technical possible area, so form 1-100%. But if the dimming area is restricted, the dimming actuator will be at least switched on with the lowest allowed value and maximum with the highest allowed value;...
  • Page 16 3.8.1 Dimming speed The dimming speed allows parameterizing the duration of the dimming process individually. The chart shows the dynamic range for this parameter: ETS-text Dynamic range Comment [default value] De nes the time for all relative dim processes 1 120s Dimming speed for relative dimming related to relative dimming process of 100%.
  • Page 17: Scene Function

    3.9 Scene function When functions of different groups (e.g. light, heating and shutter) shall be changed simultaneously with only one keystroke, it is practical to use the scene function. By calling a scene, you can switch the lights to a specific value, drive the shutter to an absolute position, switch the heating to the day mode and switch the power supply of the sockets on.
  • Page 18: Automatic Function

    The following chart shows the dynamic range for an activated scene function: Dynamic range ETS-text Comment [default value] A d j u s t s w h e t h e r t h e l e a r n i n g / s a v i n g not active Learn scene function shall be enabled for the scenes of...
  • Page 19: Block Function

    3.10.1 Submenu automatic function The further parameterization can be done at the submenu of the automatic function. Dynamic range ETS-text Comment [default value] Off, 10%, 20%, 30%, 40%, 50%, 60%, Defines the exposure value for an Automatic function 1 [4] – 70%, 80%, 90%, 100% light automatic call.
  • Page 20 3.11.1 Blocking objects For both blocking objects an action for activation as well as deactivation can be defined Dynamic range ETS-text Comment [default value] De nes the action for activation of Off, no change, Light value Behavior at Block I = Value 1 (10%,20%,30%,.., 100% the rst blocking object...
  • Page 21: Other Useful Information

    3.12 Other useful information The driver also provides some useful information including output short-circuit detection and value of power consumption. The chart shows the dynamic range for this parameter: Dynamic range ETS-text Comment [default value] active Activates output short-circuit detection Enable led driver output error detect not active Power consumption feedback...
  • Page 22 N o . 2 8 , W u q u a n 3 r d R d . , W u g u D i s t . , N e w Ta i p e i C i t y 2 4 8 , Ta i w a n...

This manual is also suitable for:

Lcm-40knLcm-60kn

Table of Contents