Testing; Commissioning (Multiburner); System Checks; User Instructions - Seeley AIRA ATH Series Installation, Operation & Service Manual

Vacuum assisted linear, double linear, u-tube, and multi-burner gas fired heating systems
Table of Contents

Advertisement

A
ATH I
O
IRA
NSTALLATION
PERATION AND
14.1.1 Heater Lockout Indicator by Connector
A 230 V signal is provided which enables the Aira
controller, BMS system, etc. to indicate the heater that
has failed. An additional wire has to be installed from the
heater lockout indicator connector to the monitoring
computer. See Page 56, Section 13.5.
Description
Connector male - Lockout Indicator
Connector female - Lockout Indicator
Wire Blue 12"
Wire Brown 12"
14.1.2 Heater Lockout Indicator by Volt Free
Connector
A volt free contact relay is closed which enables the Aira
controller, BMS system, etc. to indicate the heater that
has failed. An additional wire has to be installed from the
heater volt free connector to the monitoring computer.
See Page 56, Section 13.5.
Description
Connector male - Volt Free
Connector female - Volt Free
Wire Blue 7"
Wire Brown 7"
Wire Yellow 12"
Screw #8 x 3/8 Hex Wshr PHH Type 23
Base relay P2RF05E
Relay G2R1-SN IMO 220 V 10 A

14.2 Testing

Establish that a satisfactory purged gas supply and an
electrical supply is available to the heater. Ensure that all
time clocks and thermostats are set to call for heat.
With the gas supply cut off at the equipment isolating
cock and the electrical supply isolated by switching off at
the local switch and removing the appliance inlet plug,
open the control chamber secured by the two screws.
Loosen the sealing screw from the pressure test point
and remove the cover cap from the governor.
Turn on the gas supply and connect equipment electrical
plug. Ensure that the timer or thermostat, if fitted, are set
to call for full gas rate. Switch on at the local switch. The
sequence as described should take place. If not, refer to
detailed fault finding sequence. When flame is
established, check the gas pressure reading and adjust
if necessary. Refer to burner data label.
Check the gas pressure at the outlet of the gas valve. See
Page 73, Section 18.10.1 for pressure settings or refer to
the data plate.
Switch off the electrical supply (shutting down the heater),
remove pressure gauge - tighten pressure test point
screw, ensuring a tight gas seal. Replace governor cover
cap. Close burner side cover.

14.3 Commissioning (Multiburner)

1. Establish that a satisfactory purged gas supply and
an electrical supply is available to the heater.
2. ENSURE that all the dampers are in the fully open
position.
58 of 73
S
M
ERVICE
ANUAL
Part Number
91324000
91324001
91300011
91300012
Part Number
91324000
91324001
91300004
91300005
91300003
94961406
C1050B
C1049B

14.4 System Checks

Switch on again at the local switch to ensure smooth
ignition. Carry out the following system checks:
When running, turn off the gas supply at the appliance.
The heater will immediately shut down followed by three
ignition attempts followed by lockout.
Linear and Double Linear only:
When running, disconnect the fan plug from the burner.
The unit should shut down within three seconds, proving
operation of the pressure switch.

14.5 User Instructions

After satisfactory testing, ensure that the client is fully
aware of the operation of the system. Bring this manual to
the attention of the user or purchaser; instruct them in the
safe operation of the heater(s). Advise the user that if the
3. With the gas supply off at each of the burners and
the electrical supply isolated, open the control
chamber secured by two self tapping screws.
4. Ensure that all time clocks and thermostats are set
to call for heat.
5. Switch on the electrical supply at the main isolator.
This will start the exhaust fan.
6. Balancing Cold Vacuum
Check each burner vacuum by connecting an
inclined pressure gauge to the tee on the pressure
switch inlet side in the burner. Adjust the damper so
that the vacuum is 1.9 mbar. Repeat for each burner.
7. Starting at the end burner (furthest from the exhaust
fan), with the inclined pressure gauge connected as
described above. Turn on the gas supply and con-
nect equipment electrical plug, reset the pressure
switch by removing vacuum from the inlet side of the
pressure switch waiting several seconds and recon-
necting. The start up sequence described on Page
57, Section 14 should take place. If not, refer to
detailed fault finding sequence. When flame is
established, check the gas pressure reading and
adjust if necessary. See data label.
Check the gas pressure at the outlet of the gas
valve. See Page 73, Section 18.10.1 for pressure
settings or refer to the data plate.
Switch off the electrical supply (shutting down the
heater), remove pressure gauge - refit pressure test-
point screw, ensuring a tight gas seal. Replace gov-
ernor cover cap.
Repeat this procedure for each burner in the sys-
tem.
Close the control chamber and secure with two
sheet metal screws.
8. Balancing Hot Vacuum
Reconnect all the burners on the system and allow
them to reach full operating temperature (approxi-
mately 20 minutes). Return to each burner and
recheck the hot vacuum at the tee on the inlet to the
pressure switch. Readjust the damper so that the
hot vacuum of 1.5 mbar (2.0 mbar for ATH40EF) is
achieved and lock the damper in position.

Advertisement

Table of Contents
loading

Table of Contents