6.6

Unbrazing system components

WARNING
Explosive flame! Burning! Oil-refrigerant mixtures are highly flammable.
Remove all refrigerant before opening the system. Avoid working with an
unshielded flame in a refrigerant charged system.
Before opening up a system it is important to remove all refrigerant from both the high and low
sides of the system. If the refrigerant charge is removed from a scroll-equipped unit from the
high side only, it is possible for the scrolls to seal, preventing pressure equalization through the
compressor. This may leave the low side shell and suction line tubing pressurized. If a brazing
torch is then applied to the low side while the low side shell and suction line contain pressure,
the pressurized refrigerant and oil mixture could ignite when it escapes and contacts the brazing
flame. To prevent this occurrence, it is important to check both the high and low sides with
manifold gauges before unbrazing. Instructions should be provided in appropriate product
literature and assembly (line repair) areas. If compressor removal is required, the compressor
should be cut out of system rather than unbrazed.
7
Dismantling & disposal
Removing oil and refrigerant:
Do not disperse in the environment.
Use the correct equipment and method of removal.
Dispose of oil and refrigerant properly.
Dispose of compressor properly.

DISCLAIMER

1. The contents of this publication are presented for informational purposes only and are not to
be construed as warranties or guarantees, express or implied, regarding the products or
services described herein or their use or applicability.
2. Emerson Climate Technologies GmbH and/or its affiliates (collectively "Emerson"), as
applicable, reserve the right to modify the design or specifications of such products at any
time without notice.
3. Emerson does not assume responsibility for the selection, use or maintenance of any
product.
Responsibility for proper selection, use and maintenance of any Emerson product
remains solely with the purchaser or end user.
4. Emerson does not assume responsibility for possible typographic errors contained in this
publication.
C6.2.24/0215-0515/E
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents