AEC GPWC70 Operating Instructions Manual

Water-cooled, microprocessor controlled

Advertisement

OPERATING INSTRUCTIONS
FOR
WATER CHILLER
(Water-cooled, Microprocessor Controlled)
CE
Conformity

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GPWC70 and is the answer not in the manual?

Questions and answers

Summary of Contents for AEC GPWC70

  • Page 1 OPERATING INSTRUCTIONS WATER CHILLER (Water-cooled, Microprocessor Controlled) Conformity...
  • Page 2: Installation Notices

    OPERATING INSTRUCTIONS INSTALLATION Install this water cooled chiller on a solid foundation. The installation location should be convenient for operation and proper distance from the cooling tower. If the cooling tower is installed outdoors, make sure it is in an environment with good air convection, free of pollution and gas. If the cooling tower is installed at a factory, use an exhaust fan to keep good air convection.
  • Page 3: How To Operate The Machine

    HOW TO OPERATE THE MACHINE A. OPERATING SEQUENCE 1. Push on the Main Isolator to “1” (ON) position. 2. Push on the switch of cooling tower and indicator lamp lighting. 3. Push on the chilled water pump switch and indicator lamp lighting. Notice: The outlet ball valve of condensing water must be opened.
  • Page 5 TMP.SW. CN24 YUTING-2-B CN23 CN22...
  • Page 7 REFRIGERANT AND WATER SYSTEM DIAGRAM Description Description Temperature Sensor High Pressure Switch Water Tank Water Condenser Automatic Water Supply Pressure Release Valve Pump Motor High Pressure Gauge Water Pressure Gauge Dry Strainer Bypass Valve Expansion Valve Evaporator Mesh Filter Anti-Frozen Switch Mold Low Pressure Gauge Cooling Tower...
  • Page 8 GPWC70...
  • Page 13: Troubleshooting

    FAULT FINDING HINTS CONDITION STATUS TROUBLE SHOOTING Power is normal, no error 1.Fuse burnt out. 1.Replace the fuse. code is displayed, but 2.Microprocessor board 2.Replace PC board or set AMS switch machine does not run. faulty. Error code displays ‘00’, 1.
  • Page 14 Compressor overload 1. Abnormal voltage, or lack 1. Three phase power source voltage (Error code display ‘09’ of phase running. dropped, unstable voltage or lack of phase. or ‘10’) 2. Replace. 2. Compressor damage. 3. Reduce load. 3. Overload, or water temperature too high.
  • Page 15 APPENDIX 1: TREATMENT FOR POOR HEAT DISSIPATION Poor heat dissipation on the condenser will result in low efficiency, current consumption increase and a poor cooling effect. When pressure reaches 285 PSI, the high-pressure protection switch for the compressor will trip. The compressor stops, and error code indication 05 or 06 will display, indication poor heat dissipation.
  • Page 16: Personal Protective Equipment

    APPENDIX 5: PROTECTION SWITCH FAULTY When the error code indication displays ’00’, but the compressor does not run, check the following items: 1. Check PC1 on the microcomputer control panel for damaged. 2. Check the relay coil on the compressor for damage or poor contact, and check the overload protector for damage.