Phoenix Contact IB IL 24/230 DOR 1/W Datasheet
Phoenix Contact IB IL 24/230 DOR 1/W Datasheet

Phoenix Contact IB IL 24/230 DOR 1/W Datasheet

Interbus inline terminal with one relay changeover contact

Advertisement

Quick Links

IB IL 24/230 DOR 1/W
INTERBUS Inline Terminal
With One Relay Changeover Contact
Applies to terminals with hardware version 01 and later.
Data Sheet 5663BC01
This data sheet is only valid in
association with "Configuring and
Installing the INTERBUS Inline
Product Range" User Manual
IB IL SYS PRO UM E.
Function
The terminal is designed for use within an
INTERBUS Inline station. It has a relay
changeover contact that is electrically isolated.
The terminals can be used in the
SELV (low voltage) area and in the AC
area. Observe the appropriate
conditions and safety notes when
using the terminal in the AC area.
Features
Safe isolation according to EN 50178
Electrically isolated connection for an
actuator
Nominal current at the output: 3 A
Total current of the terminal: 3 A
Diagnostic and status indicators
5663BC01
09/2001
Figure 1
IB IL 24/230 DOR 1/W
terminal with connector
Please note that the connector is not
supplied with the terminal. Please
refer to ordering data on page 17 to
order the appropriate connectors for
your application.
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IB IL 24/230 DOR 1/W and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Phoenix Contact IB IL 24/230 DOR 1/W

  • Page 1 IB IL 24/230 DOR 1/W INTERBUS Inline Terminal With One Relay Changeover Contact Applies to terminals with hardware version 01 and later. Data Sheet 5663BC01 09/2001 This data sheet is only valid in association with “Configuring and Installing the INTERBUS Inline Product Range”...
  • Page 2: Correct Usage

    IB IL 24/230 DOR 1/W Safety Notes for Inline Terminals Used in Areas Outside the SELV (AC Area) Only qualified personnel may carry out work on recognize and avoid any possible dangers. the Inline terminals of the AC area. (Definitions for skilled workers according to EN 50110-1:1996).
  • Page 3: Installation Instructions And Notes

    Read the User Manual terminal after the Please observe the installation IB IL 24/230 DOR 1/W, if required. guidelines in the IB IL SYS PRO UM E User Manual, in particular the notes for Switching Loads in the 230 V Area the low voltage area.
  • Page 4: General Description

    2.4 are jumpered in the connector IB IL SCN-8-AC. If required, it is possible to supply several relays of the IB IL 24/230 DOR 1/W terminals by using a jumper to send the voltage from one terminal Figure 2 IB IL 24/230 DOR 1/W to the next.
  • Page 5: Internal Circuit Diagram

    IB IL 24/230 DOR 1/W Internal Circuit Diagram Key: INTERBUS protocol chip (bus logic O P C including voltage conditioning) Terminal point, without metal contact Relay Isolated area Isolated area including relay contact isolated from logic area including coils of the relay through "safe isolation"...
  • Page 6: Connection Examples

    24 V area consisting of bus terminal and I/O terminals Figure 4 Connection example of an actuator IB IL 24/230 DOR 1/W terminal separated from the 24 V area using the according terminals 24 V area consisting of power terminal and I/O terminals See also “Special Features of the IB IL 24/...
  • Page 7 Figure 7 Switching 24 V within a 24 V area 24 V area consisting of bus terminal and I/O terminals IB IL 24/230 DOR 1/W terminal 24 V area consisting of power terminal and I/O terminals 5663BC01...
  • Page 8 IB IL 24/230 DOR 1/W Interference Suppression Measures for Inductive Loads/ Switching Relays Each electrical load is a combination of ohmic, capacitive and inductive elements. When switching these loads a larger or smaller load is provided for the switching contact depending on...
  • Page 9 IB IL 24/230 DOR 1/W Circuit Versions 5663BC01...
  • Page 10 IB IL 24/230 DOR 1/W RC Circuit Versions RC Series Connection: Sizing: C   L / 4 ™ R – Capacitor: load load R   0.2 ™ R – Resistor: load RC Parallel Connection With Series Diode Sizing: C   L / 4 ™...
  • Page 11 6 A REL-SNR-1XU/G 5 GOLD LIEG) when switching on the load. This guarantees a lifetime of the IB IL 24/230 DOR 1/W terminal as Switching current in A high as possible. Switching voltage in V...
  • Page 12: Programming Data

    IB IL 24/230 DOR 1/W Programming Data ID code (189 Length code Process data channel 2 bits Input address area 0 bits Output address area 2 bits (only bit 0 is occupied) Parameter channel 0 bits (PCP) Register length (bus)
  • Page 13: Technical Data

    IB IL 24/230 DOR 1/W Technical Data General Data Housing dimensions (width x height x depth) 12.2 mm x 120 mm x 71.5 mm (0.480 in. x 4.724 in. x 2.815 in.) Weight 46 g (without connector) Operating mode Process data operation with 2 bits...
  • Page 14 IB IL 24/230 DOR 1/W Relay Output Number Contact material AgSnO , hard gold-plated 50 m W at 100 mA/6 V Contact resistance Limiting continuous current (at maximum ambient temperature) Maximum switching voltage 253 V AC, 250 V DC Maximum switching power (AC/DC)
  • Page 15 IB IL 24/230 DOR 1/W Maximum Switching Current for Ohmic Load Depending on the Switching Voltage Switching Voltage (V DC) Switching Current (A) 0.26 0.23 0.215 0.18 0.165 0.155 Load Current (I in A) as a Function of the Switching Voltage (U...
  • Page 16 IB IL 24/230 DOR 1/W Power Dissipation Formula to Calculate the Power Dissipation in the Terminal + (P ) + P = 0.19 W + (0.26 W) + I x 0.5 For a N/C contact, the term P in the formula does not apply.
  • Page 17: Ordering Data

    IB IL 24/230 DOR 1/W Safety Devices None Error Messages to the Higher-Level Control or Computer System None Air and Creepance Distances (According to EN 50178, VDE 0109, VDE 0110) Isolating Distance Creepance Test Voltage Distance Distance ˜ 5.5 mm ˜...
  • Page 18 IB IL 24/230 DOR 1/W Phoenix Contact GmbH & Co Flachsmarktstr. 8 32825 Blomberg Germany + 49 - 52 35 - 3 00 + 49 - 52 35 - 34 12 00 www.phoenixcontact.com 5663BC01...

Table of Contents