Phoenix Contact IB IL 24/230 DOR 4/W-PC Datasheet
Phoenix Contact IB IL 24/230 DOR 4/W-PC Datasheet

Phoenix Contact IB IL 24/230 DOR 4/W-PC Datasheet

Inline terminal with four relay changeover contacts

Advertisement

Quick Links

IB IL 24/230 DOR 4/W-PC
IB IL 24/230 DOR 4/W-PC-PAC
Inline Terminal
With Four Relay Changeover Contacts
Data Sheet 6530B
The IB IL 24/230 DOR 4/W-PC and
IB IL 24/230 DOR 4/W-PC-PAC only
differ in the scope of supply (see
"Ordering Data" on page 17). Their
function and technical data are identical.
For greater clarity, the Order Designation
IB IL 24/230 DOR 4/W-PC is used
throughout this document.
This data sheet is only valid in association
with the IB IL SYS PRO UM E User
Manual or the Inline System Manual for
your bus system.
Function
The terminal is designed for use within an Inline
station. It has four electrically isolated relay
changeover contacts. The terminal is suitable for
switching inductive and capacitive loads.
The terminal can be used in the SELV
area and in the AC area. Observe the
appropriate regulations and safety notes
when using the terminal in the AC area.
Please use the IB IL 24/230 DOR 4/W
terminal for switching voltages less than
12 V or currents less than 100 mA.
6530B
03/2003
Features
Safe isolation according to EN 50178
Electrically isolated connection for four actuators
Nominal current at the output: 3 A
Total current of the terminal: 4 x 3 A = 12 A
LED diagnostic and status indicators
Figure 1
IB IL 24/230 DOR 4/W-PC terminal with
connectors
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IB IL 24/230 DOR 4/W-PC and is the answer not in the manual?

Questions and answers

Summary of Contents for Phoenix Contact IB IL 24/230 DOR 4/W-PC

  • Page 1 IB IL 24/230 DOR 4/W-PC-PAC Inline Terminal With Four Relay Changeover Contacts Data Sheet 6530B 03/2003 Features The IB IL 24/230 DOR 4/W-PC and – Safe isolation according to EN 50178 IB IL 24/230 DOR 4/W-PC-PAC only – Electrically isolated connection for four actuators differ in the scope of supply (see –...
  • Page 2: Safety Notes

    IB IL SYS PRO UM E User Manual or the Inline the SELV (AC area) System Manual for your bus system. Phoenix Contact Only qualified personnel may work on accepts no liability if the device is used for anything Inline terminals in the AC area.
  • Page 3 (e.g., switching 230 V AC within a 24 V DC segment). In this case, place a distance terminal before and after the IB IL 24/230 DOR 4/W-PC terminal (see "Ordering Data" on page 17). The isolating distances between the individual areas are thus maintained.
  • Page 4: General Description

    1.2/2.2, 1.3/2.3, and 1.4/2.4 are jumpered. It is therefore possible to transmit the power to supply several relays of IB IL 24/230 DOR 4/W-PC terminals from one connector to the next via a jumper. Please note that the current at one...
  • Page 5: Internal Circuit Diagram

    IB IL 24/230 DOR 4/W-PC (-PAC) Internal Circuit Diagram Figure 3 Internal wiring of the terminal points Key: Protocol chip (bus logic including O P C Other symbols are explained in the voltage conditioning) IB IL SYS PRO UM E User Manual or in the Inline System Manual for your bus system.
  • Page 6: Connection Examples

    IB IL 24/230 DOR 4/W-PC (-PAC) Connection Examples Connecting Actuators Figure 4 Typical connection of actuators Figure 5 Output relay contacts 6530B...
  • Page 7 IB IL 24/230 DOR 4/W-PC (-PAC) Switching Voltages That Are Not Available in the Switching Voltages That Are Available in the Segment Segment The distance terminals are not required to switch a 24 V channel within a 24 V area or to switch a 230 V channel within a 230 V area.
  • Page 8: Interference Suppression Measures On Inductive Loads/Switching Relay

    IB IL 24/230 DOR 4/W-PC (-PAC) Interference Suppression Measures If sized correctly, these circuit versions do not differ greatly in their effectiveness. In principle, a protective on Inductive Loads/Switching Relay measure should be directly implemented at the source of the interference. In addition, the following...
  • Page 9 IB IL 24/230 DOR 4/W-PC (-PAC) Circuit Versions 6530B...
  • Page 10 IB IL 24/230 DOR 4/W-PC (-PAC) RC Circuit Versions RC Connected in Series: Sizing: C ≈ L /4 × R – Capacitor: Load Load R ≈ 0.2 × R – Resistor: Load RC Parallel Circuit With Series Diode Sizing: C ≈ L /4 ×...
  • Page 11 To prolong the life of the IB IL 24/230 DOR 4/W-PC terminal as mush as possible when using lamp loads or capacitive loads, the current peak must not exceed...
  • Page 12: Programming Data/Configuration Data

    IB IL 24/230 DOR 4/W-PC (-PAC) Programming Data/Configuration Process Data Data Assignment of Terminal Points to OUT Process Data INTERBUS (Byte.bit) 0.3 0.2 0.1 0.0 ID code (189 view Length code Assignment Slot Process data channel 4 bits N/C contact 1.2 1.2 1.2 1.2...
  • Page 13: Technical Data

    IB IL 24/230 DOR 4/W-PC (-PAC) Technical Data General Data Order Designation (Order No.) IB IL 24/230 DOR 4/W-PC-PAC (28 62 18 1) IB IL 24/230 DOR 4/W-PC (28 60 41 3) Housing dimensions (width x height x depth) 48.8 mm x 120 mm x 71.5 mm (1.921in.
  • Page 14 IB IL 24/230 DOR 4/W-PC (-PAC) Relay output Number Contact material AgSnO , hard gold-plated Contact resistance 50 mΩ at 100 mA/6 V Limiting continuous current (at maximum ambient temperature) Maximum switching voltage 253 V AC, 250 V DC Maximum switching power (AC/DC)
  • Page 15 IB IL 24/230 DOR 4/W-PC (-PAC) Maximum Switching Current for Ohmic Load Depending on the Switching Voltage (With Direct Voltage) Switching Voltage (V DC) Switching Current (A) 0.26 0.23 0.215 0.18 0.165 0.155 Load Current (I in A) as a Function of the Switching Voltage (U...
  • Page 16 IB IL 24/230 DOR 4/W-PC (-PAC) Maximum Switching Current Depending on the Temperature (With Alternating Voltage) With a switching current of 3 A, the switching voltage with alternating current must not exceed 253 V AC. Observe the derating. Load Current (I in A) as a Function of the Ambient Temperature (T in °C)
  • Page 17: Ordering Data

    Terminal with four relay changeover contacts IB IL 24/230 DOR 4/W-PC 28 60 41 3 Four connectors are required for the complete fitting of the IB IL 24/230 DOR 4/W-PC-PAC terminal. Connector with seven terminals, spring-cage connection IB IL SCN-8-AC-REL 27 40 29 0 (gray, w/o color print);...
  • Page 18 IB IL 24/230 DOR 4/W-PC (-PAC) Phoenix Contact GmbH & Co. KG Flachsmarktstr. 8 32825 Blomberg Germany +49 - 52 35 - 30 0 +49 - 52 35 - 34 12 00 www.phoenixcontact.com Worldwide Locations: www.phoenixcontact.com/salesnetwork 6530B...

This manual is also suitable for:

Ib il 24/230 dor 4/w-pc-pac

Table of Contents